Appendix B - Measurement Specifications
81
Voltage (Option 400V)
DC
0.1% (0.25% above 250V) + 0.1V
0.02Hz to 20Hz range
0.1% (0.25% above 250V) + 0.02V + 0.1%/Hz
add 0.15% below 0.04Hz if AC coupled
add 0.075V for peak measurements
0.2Hz to 200Hz range
0.1% (0.25% above 250V) + 0.02V + 0.01%/Hz
add 0.05% below 0.4Hz if AC coupled
add 0.075V for peak measurements
2Hz to 2KHz range
0.1% (0.25% above 250V) + 0.02V + 0.001%/Hz
add 0.05% below 4Hz if AC coupled
add 0.075V for peak measurements
20Hz to 5KHz range
0.1% (0.25% above 250V) + 0.025V + 0.4%/KHz
add 0.05% below 40Hz if AC coupled
add 0.3V for peak measurements
20Hz to 75KHz range
0.1% (0.25% above 250V) + 0.05V + 0.02%/KHz
add 0.1% below 40Hz if AC coupled
add 0.5V for peak measurements
Common Mode
>70dB decreasing linearly to >40dB at 75KHz
Current to Voltage Crosstalk
typically negligable
Voltage to Voltage Crosstalk
>120dB decreasing linearly to >80dB at 75KHz
Phase (to other phase)
0.1° + 0.025°/KHz
Voltage (Option 950V)
DC
0.1% (0.25% above 400V) + 0.15V
0.02Hz to 20Hz range
0.1% (0.25% above 400V) + 0.025V + 0.1%/Hz
add 0.15% below 0.04Hz if AC coupled
add 0.1V for peak measurements
0.2Hz to 200Hz range
0.1% (0.25% above 400V) + 0.025V + 0.01%/Hz
add 0.05% below 0.4Hz if AC coupled
add 0.1V for peak measurements
2Hz to 2KHz range
0.1% (0.25% above 400V) + 0.03V + 0.001%/Hz
add 0.05% below 4Hz if AC coupled
add 0.15V for peak measurements
20Hz to 5KHz range
0.1% (0.25% above 400V) + 0.05V + 0.4%/KHz
add 0.05% below 40Hz if AC coupled
add 0.5V for peak measurements
Summary of Contents for PA2553
Page 1: ...Powertek USER S GUIDE PA2553 PA2553E Three Phase Power Analyser ...
Page 2: ......
Page 34: ...34 PA2553 User s Guide ...
Page 50: ...50 PA2553 User s Guide ...
Page 64: ...64 PA2553 User s Guide ...
Page 78: ...78 PA2553 User s Guide ...