32
© 2001 Schneider Electric All Rights Reserved
Chapter 5—Operation
63230-314-200/A2
EGX200 Embedded Web Page Options
8/2001
Ethernet Port Setup via LAN
After you assign the initial IP address to the EGX200 through HyperTerminal or the
web browser (refer to page 8), you can go to the Communications Settings web page
via a standard web browser and change the EGX200 network setup (see Figure 5–4
on page 31). The following parameters are necessary for network setup and must be
compatible with your network:
• IP address
• subnet mask
• router address
Serial COM Port Setup
The serial COM port setup information consists of the baud rate, parity, and wiring
mode (see Table 5–2). The baud rate and parity must match the settings for attached
RS-485 devices (all devices must have the same baud rate and parity settings). Set
the mode according to whether your daisy chain is 2-wire or 4-wire. These ports are
configured independently from each other and can have different settings.
In addition, COM 2 can be set for either RS-232 or RS-485 communication. The default
setting is RS-485.
Device List
Figure 5–5 on page 33 shows the Device List page, in which serial devices can be
identified. Keep in mind the following points when setting up the Device List:
For COM 1 daisy-chain devices:
• MODBUS/JBUS devices do not have to be defined in the COM 1 column of the
Device List, although it is recommended to help you manage your system.
• POWERLOGIC protocol (SY/MAX) devices must be defined in the COM 1 column
of the Device List.
For COM 2 daisy-chain devices:
• All MODBUS/JBUS and POWERLOGIC devices must be defined.
NOTE: Each COM port device list column must be updated separately.
Table 5–2: Serial Port Setup Parameters
Parameter
Options
Default Setting
Baud Rate
1200, 2400, 4800, 9600, 19200, 38400
9600
Parity
None, Even
Even
Mode
4-Wire, 2-Wire
4-Wire
Port Selection (COM 2 only)
RS-485, RS-232
RS-485