3) Operating Environment
Temperature
Humidity
Altitude
Storage temperature
0
°
C-40
°
C
<95%
<1000m
0
°
C-40
°
C
Note: if the UPS is installed or used in a place where the altitude is
above than
1000m
, the output power must be derated in use, please
refer to the following:
Altitude (M) 1000 1500 2000 2500 3000 3500 4000 4500 5000
Derating
Power
100% 95% 91% 86% 82% 78% 74% 70% 67%