7
-
3.2 Product Specification and Performance
1) General Specification
Model
6KT 6KT-XL
10KT 10KT-XL
Power Rating
6KVA/4.2KW 10KVA/7KW
10KVA/7KW 15KVA/10.5KW 20KVA/14KW
Frequency (Hz)
50/60
50/60
50/60
50/60
50/60
Voltage
(176-276)V
AC
(176-276)V
AC
(304-478)V
AC
(304-478)V
AC
(304-478)V
AC
Input
Current
32A max.
50A max
50A max
75A max
100A max
Voltage
240VDC
240VDC
240VDC
240VDC
240VDC
Battery
Current
24A max
40A max
40A max
60A max
80A max
Voltage
208/220/230/240V
AC
Output
Current
26/27/26/25A 43/45/43/42A 43/45/43/42A 65/68/65/63A 87/91/87/83A
Dimension
(WxDxH) mm
260x570x717 260x570x717 260x570x717 260x570x717 260x570x717
Weight (kg)
90
35
93
38
39
55
55
2) Electrical Performance
Input
Model
Voltage
Frequency
Power Factor
Single-phase
46-54Hz/
56-64Hz
>0.98
(Full load)
Three-phase
46-54Hz/
56-64Hz
>0.95
(Full load)
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance.
Distortion
Overload capacity
Current
crest ratio
±
1%
0.7 lag
Synchronized
46-54Hz/ 56-64Hz in
Line mode (AC
mode)
±
0.1% of normal
frequency in Battery
mode
THD<2%
Full load
(Linear
Load)
105%-130% load transfers to
Bypass mode after 10 minutes
>130% load transfers to Bypass
mode after 1 second and
shutdown the output after 1
minute
3:1
maximum
3C 10KT-XL
3C15KT-XL
3C20KT-XL
6KT-XL/10KT-XL
3C 10KT-XL/15KT-XL/20KT-XL
Summary of Contents for 10KT
Page 23: ...Wiring diagram of 6KT XL 0KT XL 1 parallel system...
Page 24: ...Wiring diagram of 3C 1 KT XL 0 parallel system...
Page 25: ...Wiring diagram of 3C 15KT XL 20KT XL parallel system 3C...
Page 48: ...STEP 5 The output voltage would be 230VAC after the UPS is turned on...
Page 50: ...DB 9 Interface of AS400 communication protocol...
Page 54: ...10KVA Back View of 31 Back View of 31 20KVA...
Page 55: ......