background image

-

41

11. Setting by LCD Module 

The output voltage rating and frequency rating and bypass state could 
be set directly through LCD Display. The output voltage rating could be 
set to 208V , 220V, 230V and 240V. The output frequency rating could 
be set to 50Hz and 60Hz. The bypass state could be set to enable and 
disable.  But  all  the  settings  could  only  be  done  when  the  UPS  is  in 
Bypass or No Output mode. 
In Bypass or No Output mode, press the Select button on the LCD panel 
for more than one second, a flickering black round dot would be shown 
in the front of 

208V

AC

 on the screen. And if press the Select button 

continuously  again,  the  flickering  black  round  dot  would  move  to  the 
front of 

220V

AC

, next to the front of 

230V

AC

240V

AC

50Hz

60Hz

Bypass Disable

Bypass Enable

 in turn. And if press the Enter button 

for  more  than  one  second  at  this  time,  the  flickering  black  round  dot 
would  turn  to  flicker  less  and  the  output  voltage  rating  or  frequency 
rating or bypass state setting would be modified to the selected value. 
And if no any pressing on the Select or Enter button lasting for more 
than  ten  seconds,  the  flickering  black  round  dot  would  disappear,  no 
setting have be modified. 
The  only  one  voltage  rating  could  be  selected  in 

208V

AC

220V

AC

230V

AC

240V

AC

  at  any  time,  only  one  frequency  rating  could  be 

selected  in 

50Hz

60Hz

  at  any  time,  and  the  output  voltage  and 

frequency would be changed to the corresponding value after turning on 
the UPS by pressing the ON button. 
The UPS would turn into Bypass mode in several seconds after 

Bypass 

Enable

 is selected, and turn into No Output mode in several seconds 

after 

Bypass Disable

 is selected. 

*

Note

: When the output voltage rating be set to 208V, the output power 

must be derated to 90%. 
Here  is  an  example  for  changing  the  output  voltage  from  220V

AC

  to

 

230V

AC

 through the LCD panel. 

Summary of Contents for 10KT

Page 1: ...A EH R STANBUL TEL 90 216 574 1 574 FAX 90 216 574 71 14 E MAIL info powerguard co www powerguard com tr ERENK Y MAH ANKIRI SK NO 1 1 ATA EH R STANBUL TEL 90 216 574 1 574 FAX 90 216 574 71 14 E MAIL...

Page 2: ...th all warnings and operating instructions in this manual and on the unit strictly Save this manual properly Do not operate this unit before reading through all safety information and operating instru...

Page 3: ...Installation 12 5 1 Unpacking and Inspection 12 5 2 Input and output power cords and protective earth ground installation 12 5 3 Operating procedure for connecting the long backup time model UPS with...

Page 4: ...mode for all models 34 11 Setting by LCD Module 12 Communication Port 12 1 RS232 Interface 12 3 AS400 Interface Option 41 45 45 45 34 36 37 38 39 10 1 No Output mode 10 2 Bypass mode 10 3 Line mode 10...

Page 5: ...near heat Do not block ventilation openings in the UPS s housing Do not connect appliances or items of equipment which would overload the UPS e g laser printers etc to the UPS output Place cables in s...

Page 6: ...tem and of all connected loads The UPS output terminal block may be electrically lived even if the UPS system is not connected to the building wiring terminal In order to fully disconnect the UPS firs...

Page 7: ...ry measures specified below and any other measures necessary when working with batteries remove all jewellery wristwatches rings and other metal objects use only tools with insulated grips and handles...

Page 8: ...d Emission IEC EN 62040 2 Category C3 EMS ESD IEC EN 61000 4 2 Level 4 RS IEC EN 61000 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 5 Level 4 Low Frequency Signals IEC EN 61000 2 2 Wa...

Page 9: ...2 Description of commonly used symbols Some or all of the following symbols may be used in this manual It is advisable to familiarize yourself with them and understand their meaning...

Page 10: ...e alternating current from the utility power to direct current This direct current charges the batteries and powers the inverter On the basis of this DC voltage the inverter generates a pure sinusoida...

Page 11: ...83A Dimension WxDxH mm 260x570x717 260x570x717 260x570x717 260x570x717 260x570x717 Weight kg 90 35 93 38 39 55 55 2 Electrical Performance Input Model Voltage Frequency Power Factor Single phase 46 54...

Page 12: ...40 C 95 1000m 0 C 40 C Note if the UPS is installed or used in a place where the altitude is above than 1000m the output power must be derated in use please refer to the following Altitude M 1000 1500...

Page 13: ...enabled then the output terminals are supplied with voltage via the bypass if the mains power is available Select Button If the UPS system is in No Output mode or Bypass mode the output voltage range...

Page 14: ...s normally it can not be displayed Indicates the input voltage is lower than the SPEC range if the voltage is normally it can not be displayed Output Information Indicates the UPS output voltage value...

Page 15: ...r Inverter operating Information Indicates the circuit of the inverter is working Bypass operating Information Indicates the circuit of Bypass is working Output voltage and frequency and Bypass disabl...

Page 16: ...ve earth ground installation 1 Notes for installation 1 The UPS must be installed in a location with good ventilation far away from water inflammable gas and corrosive agents 2 Ensure the air vents on...

Page 17: ...gs 4 For UPS it is recommended to select the UL1015 6AWG 25mm2 wire or other insulated wire which com lies with AWG Standard for the UPS input and output wirings Note Do not use the wall receptacle as...

Page 18: ...and then disconnect the utility power supply 11 Suggest charging the batteries for 8 hours before use After connection turn the input breaker in the ON position the UPS will charge the batteries auto...

Page 19: ...mode JP1 and JP2 must be removed Important notes If the UPS is used in single mode JPI and JP2 must be connected If the UPS is used in parallel mode the Jumper between JP1 and JP2 must be removed Inpu...

Page 20: ...re of installing battery bank should be complied with strictly Otherwise you may encounter the hazardous of electric shock 1 A DC breaker must be connected between the battery pack and the UPS The ca...

Page 21: ...minimum UPS number that the total load needs X represents the redundant UPS number i e the fault UPS number that the system can handle simultaneously The bigger the X is the higher reliability of the...

Page 22: ...terminal block first and connect each output breaker to a main output breaker and then to the loads 5 Each UPS need an independent battery pack 6 Please refer to the wiring diagram in the next page a...

Page 23: ...Wiring diagram of 6KT XL 0KT XL 1 parallel system...

Page 24: ...Wiring diagram of 3C 1 KT XL 0 parallel system...

Page 25: ...Wiring diagram of 3C 15KT XL 20KT XL parallel system 3C...

Page 26: ...ntially in Line mode 3 Shutdown the units shut down sequentially in INV mode When the last one completes the shutdown action each unit will shut down the inverter simultaneously and transfer to Bypass...

Page 27: ...n into Line mode and the mode code is 02 If the utility power is abnormal the UPS will operate in Battery mode without output interruption of the UPS 2 Turn on the UPS with no utility power supplied i...

Page 28: ...off the connected loads before turning on the UPS and turn on the loads one by one after the UPS is working in INV mode Turn off all of the connected loads before turning off the UPS 6 2 Parallel Oper...

Page 29: ...r board back again 6 Turn on each UPS in turn and observe their display Make sure that each UPS displays normal and all the UPS transfer to the INV mode together Measure the voltage on the JP1 and JP2...

Page 30: ...e cover board of the parallel port on the new UPS push one end of the parallel cable into the slot of the parallel kit and screw up the connector screw the cover board of the parallel port back again...

Page 31: ...to be regulated again or you need to check that the parallel cable of the parallel kit are normal 12 Turn off each UPS in turn and after all of them transfer to the Bypass mode remove the maintenance...

Page 32: ...the cover board of the parallel port located on the UPS that need to be removed and remove the parallel cable and then screw the cover board back again 7 Close all of the input mains breakers of the r...

Page 33: ...andard model The backup time of the long backup time model is dependent on the external battery pack capacity and the load level as well as other factors The backup time of standard model may vary fro...

Page 34: ...gions of hot climates the battery should be charged and discharged every 2 months The standard charging time should be at least 12 hours Under normal conditions the battery life lasts 3 to 5 years In...

Page 35: ...e otherwise it may result in electric shock or fire 6 Make sure that there is no voltage before touching the batteries The battery circuit is not isolated from the input potential circuit There may be...

Page 36: ...The Fault code is 05 or 06 the UPS beeps continuously The UPS transfers to fault mode due to its internal fault Please contact the distributor or service center The Mode code is 03 UPS turn into Batt...

Page 37: ...s Battery aged Replace the batteries Please contact the distributor to obtain the parts and replacement service The ON button is pressed too briefly Press the ON button for more than 1 second The UPS...

Page 38: ...Fuse Open 24 Fault Code Table Bus Fault 05 Bypass STS Short 13 Inverter Fault 06 Battery SCR Short 14 Overload Fault 07 Parallel Communication Fail 15 Over temperature Fault 08 Current Un share Fault...

Page 39: ...the following diagram The information about the utility power the battery the UPS output and the load could be displayed The operating mode code of the UPS is 01 The block of BYPASS indicates the byp...

Page 40: ...of the UPS is 02 If output overloaded the load percent is shown and alarm will keep twice every second You should get rid of some unnecessary loads one by one to decrease the loads connected to the U...

Page 41: ...ery 4 seconds If the ON button on the front panel is pressed for more than 1 second again the buzzer will stop beeping in silence mode Press the ON button once again for more than 1 second to resume t...

Page 42: ...garded as a special parallel system single mode is a special parallel mode The LCD display in parallel mode is shown in the following diagram When the UPS operating in parallel mode the information in...

Page 43: ...in the following diagram The information about the utility power the battery the UPS output and the load could be displayed The symbol MODE not be shown and the symbol FAULT is shown instead in code d...

Page 44: ...Note If mode code is 10 it means that Inner Communication Fault and all the information of the UPS have not be shown except fault code information like the following diagram Communication Fault mode...

Page 45: ...han one second at this time the flickering black round dot would turn to flicker less and the output voltage rating or frequency rating or bypass state setting would be modified to the selected value...

Page 46: ...1 One flickering black round dot would appear in front of 208VAC after pressing the Select button STEP 2 The flickering dot would move to the front of 230VAC after pressing the Select button two times...

Page 47: ...he front of 230VAC would turn to flickerless after pressing the Enter button and the flickering dot would move to the next 240VAC STEP 4 The output voltage rating have been modified to 230VAC and UPS...

Page 48: ...STEP 5 The output voltage would be 230VAC after the UPS is turned on...

Page 49: ...12 3 AS400 Interface Option Except for the communication protocol as mentioned above this series UPS has AS400 card an optional accessory for AS400 communication protocol Please contact your local di...

Page 50: ...DB 9 Interface of AS400 communication protocol...

Page 51: ...ntrol any UPS on the same LAN no matter how far from the UPSs Installation procedure 1 Go to the web site http www ups software download com winpower htm 2 Choose the operation system you need and fol...

Page 52: ...erloaded in Battery mode Early warning 03 Beep twice every sec 9 BUS voltage abnormal 05 Continuously beep 10 INV abnormal 06 Continuously beep 11 Overloaded and cut off the output 07 Continuously bee...

Page 53: ...Appendix 2 Rear Panel Back view of 6KVA Back view of 6KVA XL Back view of 10KVA Back view of 10KVA XL...

Page 54: ...10KVA Back View of 31 Back View of 31 20KVA...

Page 55: ......

Reviews: