background image

Medical Air & Laboratory Air Systems – 7.5 & 10 HP Pumps

Powerex  

  150 Production Drive  

  Harrison, OH  45030  

  USA

P   1.888.769.7979  

  F   513.367.3125  

  www.powerexinc.com

IN594402AV  

  06/2017

Page 2 of 28

Components

Oil-less Scroll Compressor Pumps

Powerex  laboratory  open  scroll  systems  are  designed  to  supply 

continuous oil-free air by using the most advanced scroll technology.

The Powerex scroll compressor offers a dynamically balanced air 

end which insures vibration-free operation. The rotary design permits 

a continuous 100% duty cycle. No oil separation, oil filtration, or inlet 

valves  are  required  on  the  Powerex  Scroll  unit.  Each  compressor 

shall  be  belt  driven  oil-less  rotary  scroll  single  stage,  air-cooled 

construction with absolutely no oil needed for operation. Direct drive 

compressors shall not be used. The rotary design shall not require any 

inlet or exhaust valves and shall be rated for 100% continuous duty. 

Systems consist of multiple compressor pumps that are automatically 

controlled and alternated to equalize usage and wear.

The Powerex oil-less rotary scroll air compressor is based on the 

theory  of  scroll  compression.  A  scroll  is  a  free-standing,  intricate 

spiral bounded on one side by a solid, flat plane or base. A scroll set, 

the  basic  compression  element  of  a  scroll  compressor,  is  made  up 

of two identical spirals which form right and left hand parts. One of 

these scroll components is indexed or phased 180° with respect to 

the other so the scrolls can mesh.

Crescent-shaped gas pockets are formed and bounded by the spirals 

and  the  base  plate  of  both  scrolls.  As  the  moving  scroll  is  orbited 

around  the  fixed  scroll,  the  pockets  formed  by  the  meshed  scrolls 

follow the spiral toward the center and diminish in size. The moving 

scroll is prevented from rotating during this process so that the 180° 

phase relationship of the scrolls is maintained. The compressor’s inlet 

is at the outer boundary of the scrolls. The entering gas is trapped in 

two completely opposite gas pockets and compressed as the pockets 

move toward the center. The compressed gas is discharged through 

the outlet at the center of the fixed scroll so no valves are needed.

Each  compressor  shall  have  flexible  connectors  on  intake  and 

discharge,  an  electric  drive  motor,  a  discharge  check  valve,  an  air-

cooled  aftercooler  and  a  high  discharge  temperature  shut  down 

switch. Each compressor module shall have an isolation valve and a 

moisture separator with automatic drain.

The scroll pump is driven by a three phase electric motor and a dual 

V-belt drive.

The system includes an after cooler for each pump and condensate 

separators  connected  to  electric  timer  drain  valves.  For  NFPA99 

systems,  duplex,  isolatable  timer  drains  are  installed.  Each  pump 

module or stack of two pumps for 10 HP models is equipped with 

an isolation valve so that the pump or module may be removed for 

service and the valve closed leaving the system operable with partial 

capacity. (If the valve is used to isolate the system while a person is 

working or risk of injury exists, appropriate energy lock out tag out 

procedures must be employed.)

Controls

The  disconnects  and  protection  devices  in  the  Powerex  control 

system are for the motor branch circuits, accessory supply circuits and 

for the control circuit only. The controls on the Powerex Laboratory 

Open Scroll System do not include a service disconnect and circuit 

protection for the supply circuit. Selection and installation of these 

items must be provided in compliance to local and national codes in 

accordance with each facility’s need.

The PLC automatically alternates the lead designation and brings 

on lag pumps as needed, equalizing run time on the pumps in the 

system. The touch screen HMI (Human Machine Interface) panel on 

the front allows operation and monitoring of the system. The touch 

screen provides the user with displays showing the operating status 

and  allows  the  user  to  access  features  of  the  control  system.  The 

control panel also allows communication using the BACnet® protocol.

The  control  panel  includes  Hand-Off-Auto  selector  switches  for 

each pump so that a pump can be held on (or off). This can be useful 

if maintenance or diagnostic procedures are being performed.

The  transformer  is  sized  for  the  loads  imposed  by  the  Powerex 

factory  controls  and  should  not  be  utilized  for  any  other  purpose. 

Premium control panels utilize a backup transformer with a reserve 

transformer in use alarm.

Local  alarms  are  provided  for  low  pressure  and  general  fault 

conditions.  The  general  fault  alarm  includes  high  temperature, 

reserve transformer in use, motor overload and reserve pump in use 

(when specified). The wiring connection point for the alarms is on the 

terminal strip in the control panel box, with good conditions being 

contacts closed. (If a wire connection is lost, the result is an alarm.)

Receiver Tank

The ASME, National Board registered air receiver is provided in sizes 

from 200 to 240 gallons. Each receiver is rated at 200 psig working 

pressure.  Receivers  are  provided  with  sight  gauge,  moisture  drain 

(manual and no-loss electric), and internal lining to prevent corrosion.

The system receiver tank with bypass valves and duplex twin tower 

desiccant dryers are sized to provide adequate air storage and provide 

a pressure dew point of –40°F for laboratory systems with one dryer 

operating.  Medical  systems  are  not  intended  to  operate  with  both 

dryers simultaneously. Doing so will result in back flow into one of 

the regulators and leakage of air from that device. Laboratory systems 

have valves to allow both dryers to operate if needed.

The receiver tank is equipped with an electric timer drain that is 

powered from the main control panel. The drain has a manual test 

feature. The automatic action of the drain will be confirmed by the 

lack of water accumulation. 

Never  drill  holes  in,  or  perform  any  welding  on 

receiver  tanks  (unless  qualified  by  ASME  to  do 

so) or use them beyond the rated pressure settings. Never mount other 

machinery or equipment on receivers.

Air Dryer (Desiccant)

The regenerative desiccant consists of two (dual) towers filled with 

desiccant. Each tower is switched on and off stream, alternating the 

air  system  stream  and  then  being  regenerated.  Dry  purge  air  pulls 

moisture  from  the  desiccant  and  carries  the  moisture  out  of  the 

system. The medical system duplex twin tower desiccant dryers have 

Summary of Contents for SLAE075

Page 1: ...ndicates a potentially hazardous situation which if not avoided COULD result in death or serious injury Caution indicates a potentially hazardous situation which if not avoided MAY result in minor or...

Page 2: ...dures must be employed Controls The disconnects and protection devices in the Powerex control system are for the motor branch circuits accessory supply circuits and for the control circuit only The co...

Page 3: ...cumulates in the tank Operation at High Altitudes Compressor pumps are sensitive to reduced atmospheric pressure encountered as altitude increases Powerex will adjust the operating set points to compe...

Page 4: ...points may be selected and holes drilled in the base as needed to accommodate the design auto Operation with closed valves will damage the pump The intake isolation valves have had the handles removed...

Page 5: ...ave been firmly connected Confirm supply voltage and amps match the system requirements 4 Be sure all pressure connections are tight 5 Check to be certain all safety relief valves etc are unrestricted...

Page 6: ...tems 7 5 10 HP Pumps Powerex 150 Production Drive Harrison OH 45030 USA P 1 888 769 7979 F 513 367 3125 www powerexinc com IN594402AV 06 2017 Page 6 of 28 Medical Air Flow Schematic This is only a rep...

Page 7: ...tems 7 5 10 HP Pumps Powerex 150 Production Drive Harrison OH 45030 USA P 1 888 769 7979 F 513 367 3125 www powerexinc com IN594402AV 06 2017 Page 7 of 28 Medical Air Flow Schematic This is only a rep...

Page 8: ...tem has the touch screen controls the following section will explain how the screen can be used to control and monitor the unit operation Displays Pressure level and Dew Point level Pressure level wil...

Page 9: ...com IN594402AV 06 2017 Page 9 of 28 Record of all alarms warnings and service alerts with date and time Displays model number serial number service phone number If system is expandable use Plex Mode...

Page 10: ...888 769 7979 F 513 367 3125 www powerexinc com IN594402AV 06 2017 Page 10 of 28 Press Clock Setting and enter time and date This Screen Will Appear To Return to Run Mode This Screen Will Appear Seque...

Page 11: ...arrison OH 45030 USA P 1 888 769 7979 F 513 367 3125 www powerexinc com IN594402AV 06 2017 Page 11 of 28 Daily Load Factor Pump Maintenance At specific preset intervals service alerts for the Dew Poin...

Page 12: ...ou will be able to configure the 260MX S027 Gateway for basic operation You will set the device s network settings and parameters to the proper configuration for initial operation and physically place...

Page 13: ...ngs to connect the gateway The following steps will connect the gateway properly 1 Connect the 12 24 VDC power source to the device 2 Using the crossover cable connect the device to the PC 3 Insert th...

Page 14: ...again If you do not know the IP Address use the following procedure 1 Open an MS DOS Command Prompt 2 Type ipconfig and press enter 3 Note the IP address The previous example was 172 16 3 158 4 To te...

Page 15: ...s must be unique amongst all BACnet devices on the network 3 In the Name field enter a unique name for the device 4 The Description and Location fields are optional Filling in this information is reco...

Page 16: ...check the enable box 3 If an alarm is enabled then the Low Alarm and High Alarm must be set 4 If the value of the point falls below the Low Alarm the alarm is set and an email is generated if email i...

Page 17: ...es authentication enter in the Password for the SMTP Mail Username 5 Enter in the SMTP Server that is being used 6 Enter in the Email Address of the sender This is going to be the same field as Step 3...

Page 18: ...www powerexinc com IN594402AV 06 2017 Page 18 of 28 System Status 1 The main page shows the BACnet Point its current value and whether an alarm is set 2 The Value column will show the current value of...

Page 19: ...of any page 2 If the Username and or Password is ever forgotten click the Reset Password 3 Click Confirm Reset 4 Physically cycle power on the gateway within 15 minutes to gain access to the web page...

Page 20: ...dew point at the sensor This is easily corrected by changing or cleaning the filter Since the air from the Powerex system is filtered at the dryer exit filter problems are unlikely Installation Touchi...

Page 21: ...bushing 10 HP PU202648AV 1 8 Aftercooler SL060000AV 1 per pump 9 Check valve 7 5 HP IP087700AV 1 per pump Check valve 10 HP IS025003AV 1 per pump 10 Pump overpressure safety valve V 215100AV 1 12 Tan...

Page 22: ...ircuit breaker 7 5 HP 230 V PE000308AV 1 per motor Motor protector circuit breaker 7 5 HP 460 V PE000306AV 1 per motor Motor protector circuit breaker 10 HP 208 V PE000310AV 1 per motor Motor protecto...

Page 23: ...or less Pressure gauge Inspect Every 2 000 hours or less Tank Drain moisture Verify proper drain operation Air leaks Inspect Electric auto drains Replace Replace every 4 years Air Dryers Item Action...

Page 24: ...tlet line Then remove the braided stainless flex hose from the set Loosen the bolts holding the L brackets to the baseplate on the side you are pulling so they can lift up over the head of the rail to...

Page 25: ...y and the two slide bolts on the front edge of the base Keep enough torque on them to take up any slack between the slider and the main base but enough slack to allow the slider to move 2 Tighten the...

Page 26: ...Medical Air Laboratory Air Systems 7 5 10 HP Pumps Powerex 150 Production Drive Harrison OH 45030 USA P 1 888 769 7979 F 513 367 3125 www powerexinc com IN594402AV 06 2017 Page 26 of 28 Notes...

Page 27: ...red 7 500 hours of use whichever occurs first During such warranty period Powerex shall be fully liable for all Defects in the Products the Product Defects i e all costs of repair or replacement which...

Page 28: ...EQUENTAL PUNITIVE SPECULATIVE OR INDIRECT LOSSES OR DAMAGES WHATSOEVER ARISING OUT OF OR IN ANY WAY RELATED TO ANY OF THE PRODUCTS OR GOODS SOLD OR AGREED TO BE SOLD BY POWEREX TO BUYER TO THE EXTENT...

Reviews: