6.1.4
Protocols and Synchronization
[Modbus]
Modbus_Slave_Device_Address=1
Set according to the Modbus SCADA/master
application
Modbus_TCP_port=502
Set according to the Modbus SCADA/master
application
Modbus_Register_Start_Address=7000
Byte_Order=BIG_ENDIAN
Big Endian byte order stores the most significant
number in the first byte.
Little Endian byte order stores the least significant
number in the first byte.
BIG_ENDIAN
LITTLE_ENDIAN
[Output_Formatting]
Decimal_Separator="."
Date_Separator="/"
Time_Separator=":"
CSV_Separator=","
Set the Decimal, Date, Time, and CSV separator
characters here. These affect the PQube display,
the meters on the web interface, emails, and
output files.
NOTE:
You must still use a decimal point as the
decimal separator for all numbers that you enter in
the
Setup.ini
file.
[SNMP_Settings]
SNMPD_Polling=OFF
Toggle SNMP polling.
ON
OFF
SNMPD_Traps=OFF
Toggle SNMP traps.
ON
OFF
SNMP_Trap_Server=
SNMP_Port=161
Set the IP address and port of your SNMP trap
server.
Valid IPv4
address and port
number
SNMP_Trap_Version=v3
Choose SNMP v2c or v3 and define SNMP settings.
v2c
v3