transformer.
Current_Transformer_Ratio=1:1
Neutral_Current_Transformer_Ratio=1:1
Earth_Current_Transformer_Ratio=1:1
Current_I6_Transformer_Ratio=1:1
Current_I7_Transformer_Ratio=1:1
Current_I8_Transformer_Ratio=1:1
When using PSL CTs with 0.333V secondary
rating, the second number is the voltage.
You can use fractional values such as
100.35:0.333
If the CT ratio is high enough, your PQube will
automatically switch the units to kA.
From
1:1
to
50000:1
Current_Transformer_Ratio=
5:0.333
[Adjust_Phase_Connections]
Invert_Current_I1_Channel=OFF
Invert_Current_I2_Channel=OFF
Invert_Current_I3_Channel=OFF
Invert_Current_I4_Channel=OFF
Invert_Current_I5_Channel=OFF
Invert_Current_I6_Channel=OFF
Invert_Current_I7_Channel=OFF
Invert_Current_I8_Channel=OFF
Those tags are used to virtually invert cabling of
current inputs (swap wires), individually for each
input.
This can be useful if a wiring mistake has been
made during the commissioning.
ON
OFF
[Analog_Channel_Setup]
AN1xAN2_Energy_Mode=OFF
AN3xAN4_Energy_Mode=OFF
Toggle Analog Energy mode.
AN1-AN2 differential channel becomes Analog
Power (AN1×AN2) and Analog Energy
(AN1×AN2×Hours).
AN3-AN4 differential channel becomes Analog
Power (AN3×AN4) and Analog Energy
(AN3×AN4×Hours)