[Phase_To_Neutral_RVC_Events]
Phase_To_Neutral_RVC_Events=AUTO
Phase_To_Neutral_RVC_Threshold_In_Percent=2.5
Phase_To_Neutral_RVC_Hysteresis_In_Percent=1.5
AUTO
ON
OFF
[Phase_To_Phase_RVC_Events]
Phase_To_Phase_RVC_Events=AUTO
Phase_To_Phase_RVC_Threshold_In_Percent=6
Phase_To_Phase_RVC_Hysteresis_In_Percent=2
AUTO
ON
OFF
[Snapshot_Events]
Waveform_Snapshot_Interval_In_Hours=24
Trigger a waveform/RMS recording at scheduled
time intervals.
OFF
3
6
24
Enable_Snapshot_Harmonics=ON
Toggle Snapshot harmonic recordings
ON
OFF
Waveform_Snapshot_At_Startup=OFF
Set this tag to ON to take a Snapshot of your
electric power every time your PQube is powered
on or reset.
ON
OFF
Snapshot_Trigger_Hour=12
Define a specific time to trigger the Snapshot.
Any integer
between 0 and 23
To record at 5:00pm everyday:
Waveform_Snapshot_Interval_In_Hours
=24
Snapshot_Trigger_Hour=17
To record every 3 hours starting at
8:00am:
Waveform_Snapshot_Interval_In_Hours
=3
Snapshot_Trigger_Hour=8