PQube 3 Instruction Manual
Page 89 of 103
[HF_Impulse_Events]
HF_Impulse_Recording=OFF
Toggle high-frequency impulse detection and recording.
ON
OFF
HF_Impulse_Configuration=4-channels
Record HF impulses on one channel (L1-E) at 4MHz
sampling rate, or on 4 channels at 1MHz sampling rate per
channel.
L1-E
4-channels
HF_Impulse_Threshold_in_Volts=2000
Threshold for positive and negative HF impulse events in
Volts
Range between
200 x the PT
ratio and 5000 x
the PT ratio
[Mains_Signaling]
Mains_Signaling_Events=OFF
Mains_Signaling_Threshold_In_Volts=60
Mains_Signaling_Recording_Period_In_Seconds=60
Set up Mains Signaling events (also called ripple control)
according to the requirements of IEC 61000-4-30 Class A
Section 5.10.
Define the threshold and recording period here.
Mains_Signaling_Channel=L1
Set which channel your PQube 3 monitors the Mains
Signaling frequency on.
L1
L2
L3
Mains_Signaling_Harmonic_In_Hz=
Specify the Mains Signaling frequency of interest.
6.1.3
Network Configuration
Setup.ini Tags
Comments
Valid Values
Example
[Network_Setup]
IP_Address_Method=Use_DHCP
If you are automatically assigned an IP address by
your network, use DHCP. If you are using a static
IP, use Fixed IP.
Use_DHCP
Use_Fixed_IP
[Fixed_IP]
IP_Address=
Enter your IP address information here. This