SD750FR
POWER ELECTRONICS
58
CONTROL CONNECTION
EN
PIN
SEÑAL
DESCRIPCIÓN
EXT
.
SU
PPL
Y
1
+24Vdc
Power supply 24Vdc control card.
2
GND
GND control board.
ST
O F
U
N
C
IT
ON
3
STO 1[1]
Safety input STO 1.
4
TEST 1
Safety common input STO 1.
5
STO 2[1]
Safety input STO 2.
6
TEST 2
Safety common input STO 2.
D
IGIT
A
L IN
PU
TS
7
+24V_USER
Power supply for digital inputs. Protect against short circuit and overload. (M24Vdc,
180mA).
8
DI1
Programmable Digital Input 1 (Digital Input 1). Digital inputs are configured in the Input group.
Their status can be displayed in the visualization group. It is powered from terminal 7 or form an
external power 24Vdc supply. If an external power supply is used, the common must be
connected to terminal 29 (GND_USER). Programmable input as PNP and NPN
[2]
.
9
DI2
Programmable Digital Input 2. Same features as DI1.
10
DI3
Programmable Digital Input 3. Same features as DI1.
11
DI4
Programmable Digital Input 4. Same features as DI1.
12
DI5
Programmable Digital Input 5. Same features as DI1.
13
DI6
Programmable Digital Input 6. Same features as DI1. Besides, input configurable as digital PTC.
A
N
A
LOG
U
E I
N
PU
TS
14
GND_USUARIO
GND connection (0 V) for inputs
15
+24V_USUARIO
Supply voltage for analog inputs
16
10V_POT
10V power supply for potentiometer. Ready to supply a maximum of 2 potentiometers (R
1k
).
17
AI1+
Voltage or current Programmable Analogue Input 1 (V o mA). Configurable to 0-10Vdc, 0-20mA
or 4-20mA
[3]
.
The value of the input resistance in voltage mode is Ri =
20kΩ. The value of the input resistance
in current mode is Ri =
250Ω.
18
AI1-
Common Analog Input 1.
19
AI2+-
Voltage or current Programmable Analogue Input 2 (V o mA). Configurable to 0-10Vdc, 0-20mA
or 4-20mA.
The value of the input resistance in voltage mode is Ri =
20kΩ. The value of the input resistance
in current mode is Ri =
250Ω.
20
AI2-
Common Analog Input 2.
21
AI3+-
Voltage or current Programmable Analogue Input 3 (V o mA). Configurable to 0-10Vdc, 0-20mA
or 4-20mA.
The value of the input resistance in voltage mode is Ri =
20kΩ. The value of the input resistance
in current mode is Ri =
250Ω.
22
AI3-
Common Analog Input 3.
A
N
A
LOG
U
E
OU
TPU
TS
23
AO1+
Voltage or current Programmable Analogue Output 1 (V o mA). Configurable to 0-10Vdc, 0-20mA
or 4-20mA.
24
AO1-
Common Analog Output 1.
25
AO2+
Voltage or current Programmable Analogue Output 2 (V o mA). Configurable to 0-10Vdc, 0-20mA
or 4-20mA.
26
AO2-
Common Analog Output 2.
C
OMM
U
N
IC
A
TION
S
27
RS485 B
RS485 Modbus serial communication interface.
28
RS485 A
RS485 Modbus serial communication interface.
29
GND_USER
GND Connection.
D
IGIT
A
L OU
TPU
TS
30
RLY1 NO
Digital Output 1. Programmable change over relay (NO / NC). Potential free (Maximum: 250VAC,
8A; 30VDC, 8A).
31
RLY1 C
32
RLY1 NC
33
RLY2 NO
Digital Output 2. Programmable change over relay (NO / NC). Potential free (Maximum: 250VAC,
8A; 30VDC, 8A).
34
RLY2 C
35
RLY2 NC
36
RLY3 NO
Digital Output 3. Programmable change over relay (NO / NC). Potential free (Maximum: 250VAC,
8A; 30VDC, 8A).
37
RLY3 C
38
RLY3 NC
Summary of Contents for SD750FR
Page 1: ...SD750FR HARDWARE AND INSTALLATION MANUAL 4Q REGENERATIVE ACTIVE FRONT END DRIVE...
Page 2: ......
Page 54: ...SD750FR POWER ELECTRONICS 52 POWER CONNECTION EN Connections for frame 6...
Page 55: ...POWER ELECTRONICS SD750FR POWER CONNECTION 53 Connections for frame 7...
Page 56: ...SD750FR POWER ELECTRONICS 54 POWER CONNECTION EN Connections for frame 8...
Page 79: ......