MECHANICAL INSTALLATION
31
Clearances
Keep always the minimum passage width between the opened door of the SD750FR and the next fixed
obstacle. The minimum passage width must comply with national standards. The recommended
minimum passage width is 500 mm.
The cabinets can be installed against a wall or back-to-back with another unit in their rear and side parts.
However, Power Electronics recommends keeping a minimum passage distance of 800mm in the rear
part of the cabinet. The following figure and table show the clearances for all the SD750FR.
Note:
It is recommended to have enough space in the front side of the equipment. The distance must
be higher than the minimum distance in order to be able to move the equipment in case of need.
1
For frames over 8 consult with Power Electronics.
FRAME
1
MINIMUN CLEARANCE
(mm)
A
B
5
400
1095
6
400
1095
7
400
1625
8
400
1625