POWER ELECTRONICS
SD750FR
POWER CONNECTION
37
Power connection and wiring
CAUTION
The following installation recommendations are suitable for TN and TT grids. For IT grids refer the
dedicated section.
Otherwise, you could cause damage to equipment and personnel.
Wiring and periodic inspections should be performed at least 10 minutes after disconnecting the
input power. When removing the front cover, check that the red DC Link LED is off. Afterwards
you can remove the metal cover and check with a multimeter the following measures:
•
The voltage between the output plates U, V, W and the cabinet must be around 0V.
•
The voltage between the DC link +, - terminals and the chassis must be below 30Vdc.
Otherwise, you may get an electric shock.
The input and output busbars are labelled according to the following diagram.
The input terminals L1, L2, L3 and PE (drive power supply), output terminals U, V, W and PE (motor
power supply) must be introduced through the metal plates situated in the bottom part of the cabinet.
CAUTION
Do not drill or mechanize the gratings.
Otherwise, the drive could reduce its cooling capacity.
Check that the power transformer of the 400Vac and 480Vac drives is correctly wired.
Otherwise,
the drive will not start.
The front metal panel corresponds to the motor cables and the rear metal panel to the input cables; these
panels are not delivered neither drilled nor pre-marked to enable any configuration. Each cable must be
equipped with its own cable gland or grommet that prevent dust or moisture from entering the equipment.
Summary of Contents for SD750FR
Page 1: ...SD750FR HARDWARE AND INSTALLATION MANUAL 4Q REGENERATIVE ACTIVE FRONT END DRIVE...
Page 2: ......
Page 54: ...SD750FR POWER ELECTRONICS 52 POWER CONNECTION EN Connections for frame 6...
Page 55: ...POWER ELECTRONICS SD750FR POWER CONNECTION 53 Connections for frame 7...
Page 56: ...SD750FR POWER ELECTRONICS 54 POWER CONNECTION EN Connections for frame 8...
Page 79: ......