POWER ELECTRONICS
SD750FR
TECHNICAL CHARACTERISTICS
19
TECHNICAL CHARACTERISTICS
INPUT
Power range
[1]
132kW
–
2200kW
Voltage range
380
–
480 Vac (±10%), 690 Vac (-5/+10%)
Input frequency
50Hz/60Hz (±6%)
Input rectifier technology
IGBT
Rectifier bridge switching
frequency
2.8kHz
Displacement power factor
(DPF = cos φ)
1 (factory settings)
0.90 leading
… 0.90
lagging (adjustable)
Power factor
(PF= I
1
/I
rms
· cos φ)
0.98
Momentary power loss
> 2s (depending on the load inertia)
EMC input filter
Second environment (Industrial): (C3 Standard)
First environment (Domestic): C2 (Optional). C1 consult Power Electronics
Optional IT filter
Harmonics filter
LCL
Current THD (%)
< 3% / 5%
[2]
Regenerative
Yes
–
4 quadrant operation
OUTPUT
Output frequency
[2]
0...599 Hz
Overload capacity
Constant torque: 150% during 60s at 50ºC
Variable torque: 120% during 60s at 40ºC
Efficiency (at full load)
≥ 97%
Control method
V/Hz
VECTOR CONTROL
Open Loop. PWM speed control / torque, AVC: speed control / torque
Close Loop (Encoder): PWM speed control / torque, AVC: speed control / torque
PMSM I/f, sensorless and HEPOL (High Efficiency Performance Open Loop)
Carrier frequency
4 a 8kHz
–
PEWave
Output dV/dt filter
500 to 800V/µs
[3]
Output cable length
[4]
USC 300m, SC 150m
Dynamic brake
-
ENVIRONMENTAL
CONDITIONS
Operation ambient temperature
Minimum: -20°C
Maximum: +50°C (Heavy duty)
Minimum: -20°C
Maximum: +40°C (Normal duty)
Storage temperature
Minimum: -40°C
Maximum: +70°C
Altitude
1000m
Power altitude derating
[1]
>1000m, 1% PN (kW) per 100m; 4000m maximum (for higher altitude consult with
Power Electronics)
Ambient humidity
<95%, non-condensing
Degree of protection
IP54
[5]
, IP42
[6]
, Marine series adapted (IP44/IP54, under request)
Vibration
Amplitude: ± 1mm (2Hz-13.2Hz), ± 0.075mm (13.2Hz-57Hz)
Acceleration: 6.86m/s² (13.2Hz-57Hz), 9.8m/s² (57Hz-150Hz)
Heating resistors
Optional
PROTECTIONS
Motor protections
Rotor Locked, Motor overload (thermal model), Output current limit, Phase current
imbalance, Phase voltage imbalance, Motor overtemperature (PT100 signal), Speed
Limit, Torque Limit
Drive protections
IGBT’s Overload, Input Loss, Low Input Voltage, High Input Voltage, DC Bus Voltage
Limit, DC Bus Low Voltage, High Supply Frequency, Low Supply Frequency, IGBT
Temperature, Heat-sink overtemperature, Power supply fault, Drive thermal model,
Ground Fault, Software and Hardware fault, Analog Input signal loss (speed
reference loss), Safe stop and emergency stop
[1] Consult with Power Electronics for other configurations.
[2] THDi < 3% (THDv = 0%). Harmonics are below the limits defined in IEEE519 for all Isc / IL.
[3] For operation frequencies higher than 100Hz consult Power Electronics.
[4] SC: Shielded cable, USC: Unshielded Cable. Follow Power Electronics installation recommendations. For greater cable lengths, consult Power
Electronics.
[5] Applicable to the electronics.
[6] For stand-alone models.
[7] Certification in process.
3
Summary of Contents for SD750FR
Page 1: ...SD750FR HARDWARE AND INSTALLATION MANUAL 4Q REGENERATIVE ACTIVE FRONT END DRIVE...
Page 2: ......
Page 54: ...SD750FR POWER ELECTRONICS 52 POWER CONNECTION EN Connections for frame 6...
Page 55: ...POWER ELECTRONICS SD750FR POWER CONNECTION 53 Connections for frame 7...
Page 56: ...SD750FR POWER ELECTRONICS 54 POWER CONNECTION EN Connections for frame 8...
Page 79: ......