SD750FR
POWER ELECTRONICS
48
POWER CONNECTION
EN
FRAME
3
DRIVE
FUSES PER
PHASE (Nº X IN)
FRAME
DRIVE
FUSES PER
PHASE (Nº X IN)
400Vac
–
480Vac
690 Vac
5
SD75F0260 5BCD
1x350A
5
SD75F0160 6BCD
1x250A
SD75F0320 5BCD
1x350A
SD75F0180 6BCD
1x250A
SD75F0340 5BCD
1x350A
SD75F0210 6BCD
1x250A
6
SD75F0400 5BCD
2x350A
6
SD75F0250 6BCD
2x250A
SD75F0450 5BCD
2x350A
SD75F0310 6BCD
2x250A
SD75F0570 5BCD
2x350A
SD75F0400 6BCD
2x250A
7
SD75F0700 5BCD
3x350A
7
SD75F0480 6BCD
3x250A
SD75F0800 5BCD
3x350A
SD75F0570 6BCD
3x250A
SD75F0900 5BCD
3x350A
SD75F0680 6BCD
4x250A
8
SD75F1050 5BCD
4x350A
8
SD75F0825 6BCD
4x250A
SD75F1140 5BCD
4x350A
SD75F0930 6BCD
6x250A
SD75F1230 5BCD
4x350A
SD75F1050 6BCD
6x250A
Ground fault protection
The drive is equipped with an internal software that protect the motor and the drive against input and
output unbalanced currents. The response threshold can be set from 0% to 30% of the rated current.
For further information, see
Programming and Software Manual
.
This function is not intended to protect people against direct or indirect contacts or against fire, so an
external protection must be provided to ensure that a substantial ground fault current is promptly
interrupted. The SD750FR drives are suitable to operate with RCD components Type B, if it is required.
The EMC / EMC filters and motor cable lengths increase the earth leakage currents, so the protection
range is set according to the installation conditions. For additional information, contact Power
Electronics.
Motor thermal protection
The drive includes a motor thermal protection based on the motor performance parameters which
mathematically calculates the remaining heating capacity in the motor. When this reservoir is reduced
below the limits, this is, the motor temperature approaches the maximum, the drive automatically stops
the motor. For further information consult the
Software and Programming Manual
.
The drive includes as standard a PTC connection that permits monitor the motor temperature. Once
connected and configured, the drive could either stop the motor or generate a warning signal.
3
For frames over 8 consult with Power Electronics.
Summary of Contents for SD750FR
Page 1: ...SD750FR HARDWARE AND INSTALLATION MANUAL 4Q REGENERATIVE ACTIVE FRONT END DRIVE...
Page 2: ......
Page 54: ...SD750FR POWER ELECTRONICS 52 POWER CONNECTION EN Connections for frame 6...
Page 55: ...POWER ELECTRONICS SD750FR POWER CONNECTION 53 Connections for frame 7...
Page 56: ...SD750FR POWER ELECTRONICS 54 POWER CONNECTION EN Connections for frame 8...
Page 79: ......