MAN-230000-00 REV B
53
Notes:
1. Power Designers USA LLC recommends that the default values not be changed.
2. The
Precharge High/Low
voltage limits function is an optional feature that, if
enabled, maintains the charger output voltage between the precharge low and
precharge high voltage limits. This eliminates any inrush current or sparking that
can result when connecting a battery to the charger. The inrush current is caused
by the rapid charging of the output filter capacitor upon connection to a battery.
3.
Use PT Params
should be selected (YES) when charging batteries equipped
with the
PowerTrac™
monitor and when charging batteries of different voltages
or amp-hour capacities using the same charger.
4. The
Delay Start Timer
is used in conventional charging to allow battery cool
down prior to starting a charge cycle. Enter the desired time delay in minutes.
Default is 0 minutes.
5.
Additional Power Limit
and
Time of Day
functions are available to reduce
energy usage and costs by setting the charger to operate only after the local
utility’s peak demand period, thus avoiding or minimizing peak demand charges.
Contact Power Designers USA LLC for details.