MAN-230000-00 REV B
16
Figure 13: Charger electrical connection points
8. Verify the line and ground connections of the outlet or junction box/disconnect.
9. With the charger switch
OFF
, energize the source circuit and verify proper AC
voltage at the line side of the charger switch. All line-to-line voltages should be
400
–480 VAC ± 10% and matched within 10 VAC. De-energize the source
circuit.
10. Verify that the source circuit is locked and tagged out. Replace the top cover on
the charger, securing it with the four mounting screws.
THE CHARGER IS NOW READY FOR OPERATION
AC knockout
480 VAC
3
GND