Powered by Safety
®
31
Usage
01.4IB.48040C
1) MODBUS RTU (RS-485 2 Wire)
In order to make a MODBUS RTU
connection, use
E. Connect Network and Power Wiring,
4) Connect Communication Wiring (Two Wire
as a guide for the physical
connection of the device. It is assumed the
user has a basic working knowledge of the
MODBUS parameters, therefore, only the
salient details of the implementation on
the G3 are provided. A detailed MODBUS
register listing is provided in
Table M MODBUS RTU Parameters
Parameter
Default
Value
Range/Options
Baud Rate
19200
Baud
9600, 19200, 38400
Baud
Data Bits
8
N/A
Parity
None
N/A
Stop Bits
1
N/A
Max # of Registers per
Query
N/A
32
Max Polling Rate
3 Seconds
N/A
2) MODBUS TCP / IP
In order to make a MODBUS TCP/IP
connection, use
E. Connect Network and Power Wiring,
6) Connect Communication Wiring (Modbus
as a guide for the
physical connection of the device. It is
assumed the user has a basic working
knowledge of the MODBUS TCP parameters,
therefore, only the salient details of the
implementation on the G3 are provided.
A detailed MODBUS register listing is
provided in
.
Table N MODBUS TCP/IP Parameters
Parameter
Default
Value
Range/Options
IP Address
192.168.1.50
XXX.XXX.XXX.XXX (XXX
is 0-255)
Port
502
1-9999
3) Basic MODBUS Queries
The information in
is intended to
provide several basic examples of queries
that can be issued to the G3 Conversion
Modules. The examples are far from
exhaustive.
Table O Basic MODBUS Queries
Type
Read
Client ID 1,
Ch 1
Read
Client ID 1,
Ch 1
Temperature °F
Read
Client ID 1,
Ch 1
Registers
Client ID
1
1
1
MODBUS
Function
04
(Read Input
Registers)
04
(Read Input
Registers)
04
(Read Input
Registers)
Quantity
1
1
18
Start
Address
97
115
79
Absolute
Address
30098
30116
30080-30097
4) Basic Ethernet I/P Queries
The conversion module can communicate
using the CIP through Ethernet I/P. This
requires an Ethernet connection to the host
device. An EDS is provided to assist with
the setup. Ensure that desired IP address
information is accessible.
Refer to
for details.
Summary of Contents for BriteSpot BSG3
Page 1: ...Instruction Bulletin 01 4IB 48040C BriteSpot BSG3 Powered by Safety ...
Page 4: ...Powered by Safety BriteSpot BSG3 01 4IB 48040C This page is intentionally left blank ...
Page 10: ...Powered by Safety BriteSpot BSG3 01 4IB 48040C This page is intentionally left blank ...
Page 37: ...Powered by Safety 27 Usage 01 4IB 48040C Figure 34 LCD Menu and Navigation ...