background image

User’s

Manual

2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 Japan

http://www.yokogawa.com/ns/powercert/im/

You can download the latest manuals from the following website:

Model UPM101

Universal Power Monitor

(With Dedicated CT) 

<Installation> 

IM 77C01J01-00EN

2nd Edition: Mar. 2019 (YK) 

This manual describes the operating precautions, mounting procedures, wiring 

procedures and other information regarding the UPM101 Universal Power Monitor.

In this manual, illustrations related to the mounting procedures show the UPM101 

which has display function. In the related user's manuals, illustrations related to 

the descriptions of user operations show the UPM100 which has display function.

Introduction ------------------------------------- P. 1

1. For Safe Use ----------------------------------- P. 1

2. Product Specifications and the

Package Contents ---------------------------- P. 1 

3. Installation Procedures ---------------------- P. 2

4. External Wiring --------------------------- P. 2-P.3

5. UPM101 Main Specifications --------------- P. 4

IM 77C01J01-00EN

Introduction 

Thank you for purchasing our UPM101 Universal Power Monitor. The user's manuals listed 

below are supplied with the UPM101. Read the manuals thoroughly before using the UPM101 

to ensure correct and safe use. After reading the manuals, always keep them in an easily 

accessible convenient place for later reference.

Related User's Manuals and Main Information Included in Manuals

Product user’s manuals can be downloaded or viewed at the following URL. To view the user’s

manual, you need to use Adobe Reader 7 or later by Adobe Systems.

URL: http://www.yokogawa.com/ns/powercert/im/

Title

Description

Document Number

Installation

This manual describes operating precautions, 

mounting procedures, and external wiring procedures. 

It also presents the main UPM101 specifications 

(including optional specifications).

IM 77C01J01-00EN

Initial Setup Operations

This manual describes the setting procedures and 

setting ranges for various parameters (VT ratio, CT 

ratio, etc.), which pertain primarily to UPM100 and 

UPM101 which have display function.

 Measured Value Display 

Operations

This manual describes the display procedures and 

measuring ranges for various measured values (active 

energy , etc.), which pertain primarily to UPM100 

and UPM101 which have display function. It also 

provides information on various error messages and 

procedures for handling errors.

Parameter Maps

This manual provides illustrations showing the flow 

of measured value display and parameter setting 

display. It also presents lists of the measuring ranges 

and parameter setting ranges.

Model UPM100, UPM101 

Universal Power Monitor 

Communication Functions

This manual describes the communication functions 

of UPM100 and necessary information for creating 

communication program.

IM 77C01H01-10EN

1.  For Safe Use

The following symbols are indicated on the product to ensure safe use. 

This symbol on the product indicates that the operator must refer to an 

explanation in the user’s manual in order to avoid the risk of injury or death of 

personnel or damage to the instrument. The manual describes how the operator 

should exercise special care to avoid electric shock or other dangers that may 

result in injury or loss of life.

This label denotes that a protective ground terminal is necessary . Be sure to 

ground this terminal before operating the instrument.

The following symbols are used in the user’s manuals. 

 CAUTION

Indicates that operating the hardware or software in a particular manner may 

damage it or result in a system failure.

 CAUTION

Draws attention to information that is essential for understing the operations and/

or features of the product.

2. 

Product Specifications and the Package Contents 

2.1 

Model and Specifications Check

Make sure the model and suffix codes shown on the name plate attached to the UPM101 

match your order.

Model

Suffix Code

Description

UPM101

-x

x

x

x

x

-2

0

Universal Power monitor (with dedicated CT)

Phase and Wire 

Type

-1

Single-phase 2-wire (with dedicated one CT)

-2

Single-phase 3-wire (with dedicated two CTs)

-3

Three-phase 3-wire (with dedicated two CTs)

-4

Three-phase 4-wire (with dedicated three CTs)

Rated Input Voltage/

Current

4

220V/5A AC  

(phase voltage 127V AC for three-phase 4-wire) 

1

6

440V/5A AC  

(phase voltage 277V AC for three-phase 4-wire)

Output Function

0

Without display function, without pulse output

1

With display function, without pulse output

2

Without display function, with pulse output

3

With display function, with pulse output

Optional Communication Function 0

None (RS-485 communication is provided as standard)

Optional Measuring Function 

0

Integral resolution kWh

1

Integral resolution kWh / power factor

2

Integral resolution kWh 

2

 / reactive power, integrated 

reactive power

3

Integral resolution kW 

2

 / power factor, reactive power, 

integrated reactive power

4

Integral resolution Wh

5

Integral resolution Wh / power factor 

6

Integral resolution Wh 

2

 / reactive power, integrated 

reactive power

7

Integral resolution Wh 

2

 / power factor, reactive 

power, integrated reactive power

Power Supply

-2

85 to 264V AC 50/60Hz

Fixed Code

0 Always “0”

1: 200V (100V + 100V) for single-phase 3-wire. 

2: The unit is “kvarh” or “varh” when reactive power is selected. 

2.2  UPM101 Rated Power (Secondary-side Rated Power) 

Rated Power

Rated Input Voltage/Current 

Phase and Wiring

Suffix Code

4

6

1

1000W

2000W

2

1000W

3

2000W

4000W

4

2000W

4000W

2.3  Checking the Package Contents 

The UPM101 is carefully inspected before shipping. When you receive your UPM101, check its 

exterior to see if there is any damage. Also make sure a complete set of the following items is 

included in the package.

(1) UPM101

(3) User's Manua

     (Precautions on the Use of the Power Monitor Series)

They are attached to the UPM101 when shipped.

(4)Terminal Covers

(2) Dedicated CT

1 CT for single-phase 2-wire

2 CTs for single-phase 3-wire or three-phase 3-wire

3 CTs for three-phase 4-wire

(1) UPM101 (main unit): 1 

(2) Dedicated CT : 1 CT for single-phase 2-wire 

 

  2 CTs for single-phase 3-wire / three-phase 3-wire 

 

  3 CTs for three-phase 4-wire 

(3) User's Manuals: 1 set

Name 

Document Number 

Precautions on the Use of the Power Monitor Series

IM 77C01H01-91Z1

(4)  Terminal covers: 2 (with M3 screws) (The covers are attached to the UPM101 when 

shipped.) 

1

Summary of Contents for UPM101

Page 1: ...ribes how the operator should exercise special care to avoid electric shock or other dangers that may result in injury or loss of life This label denotes that a protective ground terminal is necessary...

Page 2: ...d crimp on terminals for use in connecting to the input and power supply terminals B d 2 d 2 B Round Type Open end Type Round Type Specification Size d 2 Size B Recommended Tightening Torque Applicabl...

Page 3: ...1L 2S 2L 3S 3L Dedicated CT RS 485 Signal ground Power supply Pulse output 1 of electric energy Pulse output 2 of electric energy Load Established instruments Established CT Established CT Fuse Dedica...

Page 4: ...rgy 2 of rdg with rated input Active energy 2 of rdg with rated input integration not performed on minus side Reactive energy 2 of rdg with rated input for UPM101 with optional measuring function Rege...

Page 5: ...about 5 seconds and then the display is changed to the measured value display To change measured value display To change to the parameter setting display Each time you press the SET ENT key on the mea...

Page 6: ...hat the product of the ratio does not exceed 9999 MW by calculated by secondary side rated power VT ratio CT ratio For the UPM101 set the CT ratio of the established CT where the dedicated CT is to be...

Page 7: ...d display the next parameter Next press the Move key to make the first digit flash Hold the SET ENT key down for about 3 seconds to return to the measured value display 6 2 Settings Related to Integra...

Page 8: ...splay the parameter set value Press the Up key or Down key to display ON or OFF After setting the parameter press the SET ENT key once All digits flash confirmation display Press the SET ENT key on th...

Page 9: ...Integral resolution kWh Down key Move key Up key SET ENT key Measured value display Communication light Power light COS light RST light Integrated pulse light Unit light IMPORTANT Pressing this switch...

Page 10: ...rgy 3 1 Resetting Voltage Maximum Minimum Values and Current Maximum Value The following procedure simultaneously resets voltage maximum value voltage minimum value and current maximum value Measured...

Page 11: ...Energy Apparent Energy Optional Electric Energy Instantaneous Active Regenerative Power Instantaneous Reactive Power Instantaneous Apparent Power Instantaneous Voltage Instantaneous Current Instantan...

Page 12: ...A 100VA or greater but less than 1kVA 0 0 to 999 9 VA 1kVA or greater but less than 10kVA 0 to 9999 VA 10kVA or greater but less than 100kVA 0 00 to 99 99 kVA 100kVA or greater but less than 1MVA 0 0...

Reviews: