background image

User’s

Manual

Model UPM100, UPM101

Universal Power Monitor

<Initial Setup Operations>

This manual describes the parameter setting procedures, measured value display 

procedures and measuring ranges. The explanations of user operations in this manual 

assume the UPM100 or UPM101 has display function. Parameter settings on UPM100 

or UPM101 without display function are made through RS-485 communication.

1. Front Panel and Its Functions -------------- P.1 

2. Conventions Used in This Manual 

  and Basic User Operations ----------------- P.1 
3. Action Flow on Parameter Setting 

  Display ------------------------------------------- P.1 

4. VT Ratio and CT Ratio Settings ----------- P.2 

5. Settings Related to Communication ------ P.2

6. Settings Related to Electric Energy ------ P.3 

7. Standby Mode Settings ---------------------- P.4 

1.  Front Panel and Its Functions

In the diagram below, the switch cover, which is attached to part A, is opened so that operation 

keys (8) through (12) can be seen.

5

6

7

2

3

4

1

8

9

10 11

A

12

<UPM100 without Display Function>

IMPORTANT

Pressing switch (12) resets all measured

values other than active energy,

apparent energy, regenerative energy

and reactive energy.

Inside the cover on part (A), there are only

DIP switches needed for communication

settings.

Available display lights are (2), (3), and (6),

as shown on right.

(1) Measured value display:   During operations, measured values are displayed in this area. During 

parameter settings, parameters and their settings are displayed here. 

When an error occurs, the display shows the error message. (See “4. 

Troubleshooting” in the Measured Value Display Operations User’s 

Manual.)

(2) Communication light:  

This light (green LED) turns on while communication is in progress.

(3) Power light:  

 This light (green LED) turns on while the power is on. If a communication 

error occurs, this power light flashes (four times per second) until normal 

status is restored.

(4) COS φ light:  

 This light turns on while the instantaneous power factor (optional 

measuring function) is displayed.

(5) RST light:  

 This light (red LED) turns on while voltage and/or current values are 

displayed. For example, the “S” light turns on while the S phase voltage 

value is displayed with a three-phase 4-wire setup.

(6) Integrated pulse light:    This light (green LED) flashes to match the pulse output when integrated 

pulses of each power are being output.

(7) Unit light:  

 This light turns on as the unit corresponding to the measured value. For 

example, if the measured value is **** kW, then “k” and “W” lights turn on.

(8) SET/ENT key:  

This key is used to switch displays and enter parameter settings.

(9) Move key:  

 This key is used to change a phase when measured value is displayed or 

to move the digit position (decimal point position) when setting a parameter.

(10) Up key:  

 This key is used to change the set value when setting a parameter. 

Pressing this key increases the numeric value.

(11) Down key:  

 This key is used to change the set value when setting a parameter. 

Pressing this key decreases the numeric value.

(12) Reset switch:  

 This switch restarts the UPM100. Pressing this switch resets 

all measured values other than active energy, apparent energy, 

regenerative energy and reactive energy.

2.  Conventions Used in This Manual and Basic User Operations

2.1  Conventions Used in This Manual

The following operation keys appear in this manual:

 is the <SET/ENT> key.   

 is the <Move> key.   

 is the <Up> key.   

 is the <Down> key.

2.2  Basic Operations

Measured Value Display

Parameter Setting Display

Display after Power-on

After the UPM100 is turned on, the station number (initial setting: 01)

appears for about 5 seconds and then the display is changed to the

measured value display.

<To change measured value display>

<To change to the parameter setting display>

Each time you press the <SET/ENT> key on the measured

value display, the measured value display changes in a set

sequence. After the final measured value is displayed, the

first measured value (active energy) is displayed again.

Hold the <SET/ENT> key down for about 3 seconds on the

measured value display to change to the parameter setting

display.

Press the <SET/ENT> key once on the parameter setting

display to display the “set value” for the parameter.

Press the <SET/ENT> key in the set value display to

display the “confirmation display” for the set value.

Press the <SET/ENT> key on the confirmation display to

enter the set value and display the next parameter.

The display changes to the measured value display if you

hold the <SET/ENT> key down for about 3 seconds on the

parameter setting display or do not press any key for about

5 minutes.

3.  Action Flow on Parameter Setting Display

A

B

A

B

A

A

A

A

A

A

A

A

A

A

A

A

A

A

Hold down for

about 3 seconds.

If there is no key action on the parameter

setting display for about 5 minutes, the display

changes to the measured value display.

Option

Option

Option

Option

Option

Option

(1)

(2)

(3)

(1)

(2)

(3)

(4)

Various measured values are displayed on this display. Each

time you press the <SET/ENT> key, the displayed measured

value changes. Hold the <SET/ENT> key down for about 3

seconds on the measured value display to change to the

parameter setting display.

Display

Action Flow

Power-on

After the address

(station number) is

displayed for about 5 

seconds, a measured

value is displayed.

Set value change display

Set value confirmation display

Fix the value (next parameter

will be displayed)

Decimal point position change

display
Set numeric value change

display

Set value confirmation display

Fix the value (next parameter

will be displayed)

<Display Flow for Each Parameter>

Parameter Setting

Display

Measured Value Display

Parameter (Display)

Parameter Setting Item and Reference in this Manual

Sets the VT ratio.

See “4. VT “Ratio and CT Ratio Settings.”

Sets the CT ratio.

See “4. VT “Ratio and CT Ratio Settings.”

Sets the RS-485 communication protocol.

See “5. Settings Related to Communication.”

Sets the RS-485 communication address (station).

See “5. Settings Related to Communication.”

Sets the RS-485 communication parity.

See “5. Settings Related to Communication.”

Sets the RS-485 communication stop bit.

See “5. Settings Related to Communication.”

Sets the RS-485 communication data length.

See 5. “Settings Related to Communication.”

Sets the integral low-cut power.

See “6. Settings Related to Electric Energy.”

Sets the pulse unit-1 of electric energy.

See “6. Settings Related to Electric Energy.”

Sets the ON pulse width-1 of electric energy.

See “6. Settings Related to Electric Energy.”

Sets the LAG/LEAD/REGENE of electric energy pulse.

See “6. Settings Related to Electric Energy.”

Sets the pulse unit-2 of electric energy.

See “6. Settings Related to Electric Energy.”

Sets the ON pulse width-2 of electric energy.

See “6. Settings Related to Electric Energy.”

Sets the standby mode.

See “7. Standby Mode Settings.”

Sets the standby mode timer period.

See “7. Standby Mode Settings.”

Sets the RS-485 communication baud rate.

See “5. Settings Related to Communication.”

This symbol means the output function, communication function, measured value 

function. The parameter with this symbol indicated will not be displayed for 

the UPM100 without the output function.

In this manual, the “UPM100” means the “UPM100” or “UPM101,”

and the illustrations show the “UPM100 with display function.”

5

IM 77C01J01-00EN

Summary of Contents for UPM101

Page 1: ...ribes how the operator should exercise special care to avoid electric shock or other dangers that may result in injury or loss of life This label denotes that a protective ground terminal is necessary...

Page 2: ...d crimp on terminals for use in connecting to the input and power supply terminals B d 2 d 2 B Round Type Open end Type Round Type Specification Size d 2 Size B Recommended Tightening Torque Applicabl...

Page 3: ...1L 2S 2L 3S 3L Dedicated CT RS 485 Signal ground Power supply Pulse output 1 of electric energy Pulse output 2 of electric energy Load Established instruments Established CT Established CT Fuse Dedica...

Page 4: ...rgy 2 of rdg with rated input Active energy 2 of rdg with rated input integration not performed on minus side Reactive energy 2 of rdg with rated input for UPM101 with optional measuring function Rege...

Page 5: ...about 5 seconds and then the display is changed to the measured value display To change measured value display To change to the parameter setting display Each time you press the SET ENT key on the mea...

Page 6: ...hat the product of the ratio does not exceed 9999 MW by calculated by secondary side rated power VT ratio CT ratio For the UPM101 set the CT ratio of the established CT where the dedicated CT is to be...

Page 7: ...d display the next parameter Next press the Move key to make the first digit flash Hold the SET ENT key down for about 3 seconds to return to the measured value display 6 2 Settings Related to Integra...

Page 8: ...splay the parameter set value Press the Up key or Down key to display ON or OFF After setting the parameter press the SET ENT key once All digits flash confirmation display Press the SET ENT key on th...

Page 9: ...Integral resolution kWh Down key Move key Up key SET ENT key Measured value display Communication light Power light COS light RST light Integrated pulse light Unit light IMPORTANT Pressing this switch...

Page 10: ...rgy 3 1 Resetting Voltage Maximum Minimum Values and Current Maximum Value The following procedure simultaneously resets voltage maximum value voltage minimum value and current maximum value Measured...

Page 11: ...Energy Apparent Energy Optional Electric Energy Instantaneous Active Regenerative Power Instantaneous Reactive Power Instantaneous Apparent Power Instantaneous Voltage Instantaneous Current Instantan...

Page 12: ...A 100VA or greater but less than 1kVA 0 0 to 999 9 VA 1kVA or greater but less than 10kVA 0 to 9999 VA 10kVA or greater but less than 100kVA 0 00 to 99 99 kVA 100kVA or greater but less than 1MVA 0 0...

Reviews: