Powered by Safety
®
40
Appendix A
01.4IB.48040C
BriteSpot™ BSG3
APPENDIX A - MODBUS and EIP Memory Map
MODBUS and EIP Memory Map
Range: 30005 to 30016
Category
Register
Name
Read/
Write
Register
Type
Description
Default
Range, Format
UOM
Register #
Modbus
Offset #
EIP Offset
*2
Interpretations
G-HSM-9M G-HSM-9SM G-HSM-18K
EIP
Instances
General Parameters
PCB Serial
No. LSB
R
Input
LSW of Serial Number
N/A
0-65535
N/A
30005
4
0
N/A
x
x
x
D
evic
e I
nstanc
e 101 (siz
e: 24 b
yt
es)
PCB Serial
No. MSB
MSW of Serial Number
N/A
30006
5
1
HW P/N
HW Part Number
10121
30007
6
2
FW Rev
FW Revision
N/A
30008
7
3
System Time
Day
R
Input
Device Days from RTC
N/A
1-31
N/A
30009
8
4
N/A
x
x
x
Month
Device Months from RTC
1-12
30010
9
5
Year
Device Years from RTC
2000-2009
30011
10
6
Hour
Device Hours from RTC
0-23
30012
11
7
Min
Device Minutes from RTC
0-59
30013
12
8
Sec
Device Seconds from RTC
0-59
30014
13
9
Board Parameters
Mem
Capacity
R
Input
Amount of Log Storage
Memory
N/A
0-100
%
30015
14
10
N/A
x
x
x
BMO
Board Map 0 for determining
the type of HSM configuration
0x0000-0x003F
N/A
30016
15
11
Range: 30022 to 30026
Category
Register
Name
Read/
Write
Register
Type
Description
Default
Range, Format
UOM
Register #
Modbus
Offset #
EIP Offset *2
Interpretations
G-HSM-9M G-HSM-9SM G-HSM-18K
EIP
Instances
Comm Parameters
Instance
R
Input
EIP User Assembly Instance
102
0-65535
N/A
30022
21
N/A
N/A
x
x
x
N/A
MB Port
MODBUS Port
502
1-9999
N/A
30023
22
x
x
x
MB Baud L
MODBUS Baud Rate Low Word
19200
9.6K / 19.2K /
38.4K
Baud
30024
23
x
x
x
MB Baud H
MODBUS Baud Rate High Word
0
9.6K / 19.2K /
38.4K
Baud
30025
24
x
x
x
MB Client
ID
MODBUS Client ID
1
1-31
N/A
30026
25
x
Range: 30027 to 30028
Category
Register
Name
Read/
Write
Register
Type
Description
Default
Range, Format
UOM
Register #
Modbus
Offset #
EIP Offset *2
Interpretations
G-HSM-9M G-HSM-9SM G-HSM-18K
EIP
Instances
Log Time
R
Input
Log Interval (minutes)
5
0-1440
Minutes
30027
26
N/A
N/A
x
x
x
N/A
Timer
Tick Timer (100 ms)
N/A
0-65535
Seconds
30028
27
x
x
x
Range: 30029 to 30037
Category
Register
Name
Read/
Write
Register
Type
Description
Default
Range, Format
UOM
Register #
Modbus
Offset #
EIP Offset *2
Interpretations
G-HSM-9M G-HSM-9SM G-HSM-18K
EIP
Instances
Ethernet Parameters
IP H
R
Input
High Word of the IP Address
169.254
0x0000-0xFFFF
N/A
30029
28
N/A
The values must
be parsed, each
register contains
the MSB and LSB
of the address. For
example if IP H
is 0xA9FE the IP
address would start
with A9->169 and
FE->254.
x
x
x
N/A
IP L
Low Word of the IP Address
001.001
30030
29
Mask H
High Word of the Subnet Mask 255.255
30031
30
Mask L
Low Word of the Subnet Mask
000.000
30032
31
Gate H
High Word of the Gateway
169.254
30033
32
Gate L
Low Word of the Gateway
001.001
30034
33
MAC 1
First 2 Bytes of the MAC
Address
0x3B A4
30035
34
The MAC address
should be parsed
starting with the
MSB of MAC 1 to
the LSB of MAC 3.
For example using
defaults would be
3B:A4:24:Fx:xx:xx
MAC 2
Second 2 Bytes of the MAC
Address
0x24 Fx
30036
35
MAC 3
Third 2 Bytes of the MAC
Address
N/A
30037
36
Summary of Contents for BriteSpot BSG3
Page 1: ...Instruction Bulletin 01 4IB 48040C BriteSpot BSG3 Powered by Safety ...
Page 4: ...Powered by Safety BriteSpot BSG3 01 4IB 48040C This page is intentionally left blank ...
Page 10: ...Powered by Safety BriteSpot BSG3 01 4IB 48040C This page is intentionally left blank ...