Installation Requirements
Balanced Flue Models
1.4
Air Supply
The air requirements must meet BS 5440 Part 2.
The room in which the boiler is installed does not require a
purpose provided air vent.
If the boiler is installed in a compartment, permanent air
vents are required in the compartment, one at high level
and one at low level, either direct to the outside air or to a
room. Both high level and low level air vents must
communicate with the same room or must be on the same
wall to outside air. Both the high level and low level vent
must each have a combined free area in accordance with
Table 3.
If the boiler is installed in a compartment with a door, allow
at least 25mm clearance between the front of the boiler and
the door for air movement.
1.5
Flue Systems & Terminal Location
Horizontal - Concentric (Left, Right or Rear).
The flue/terminal assembly supplied is suitable for a
wall thickness of between 150mm and 400mm.
A flue/terminal assembly suitable for a wall thickness of
up to 600mm is also available.
Both the flue/terminal assemblies are telescopic and
the minimum lengths (150 mm/6 in) are achieved by
cutting.
A 1m flue extension is available. Under no circumstances
should the total flue length exceed:-
3.4m 40 to 70 models
2.4m 80 model
1.4m 90 model
1.0m 100 model
Vertical - Concentric.
3.4m 40 - 70 models Only
Where bends may be being used, the total flue length will
be reduced, see Pages 17 & 18 for more details.
See separate Installation Instructions supplied with the
flue.
Fig. 5
Table 3
Compartment Ventilation
Free Area cm sq.
High Level
Low Level
RSL40
132
132
RSL50
165
165
RSL60
198
198
RSL70
231
231
RSL80
264
264
RSL90
297
297
RSL100
331
331
Note: If ventilating directly to outside, the figures shown in
Table 3 can be halved.
Summary of Contents for Kingfisher Mf CFL40 - 100
Page 13: ...Publication No 5102977 13 CON0093B Installation Requirements Fig 8 Fig 7 ...
Page 14: ...Publication No 5102977 14 Installation Requirements Fig 9 Fig 10 ...
Page 31: ...Publication No 5102977 31 Fig 30 Pictorial Wiring Diagram CON0082B T T B CFL Models Only ...
Page 34: ...Publication No 5102977 34 Fault Finding ...