Publication No. 5102977
10
•
Where a horizontal flue is sited less than 2m
above a balcony, above ground, or above a flat
roof to which people have access, a suitable
terminal guard must be fitted. This serves two
purposes, to protect the terminal against damage
or interference and to protect passers-by. A
terminal guard is available (Sales Code:
PTERMGUARDEF), this should be fitted centrally
about the terminal.
Note: Where a flue terminal is installed less than
1 metre from a plastic, or painted gutter, or 500
mm from painted eaves, an aluminium shield 1
metre long, should be fitted to the underside of the
gutter or painted surface. A suitable wall plate
should be fitted to the painted wall surface of a
mobile home.
•
IMPORTANT: It is absolutely ESSENTIAL, to
ensure that products of combustion discharging
from the terminal cannot re-enter the building, or
any other adjacent building, through ventilators,
windows, doors, natural air infiltration, or forced
ventilation/air conditioning. If products of
combustion are found to be re-entering any building,
the appliance MUST be turned OFF
IMMEDIATELY.
Installation Requirements
Fig. 6
M
G
G
H
F
L
G
A
A
F
J
K,N
D
E
J
Likely flue positions requiring
a flue terminal guard
C
Q
A
G
K,N
G
FLU0002A
P
S
R
Fanned Draught Balanced Flue
A
Directly below an opening, air brick,
opening window etc
B
Above an opening, air brick, opening window, etc
C
Horizontally to an opening, air brick,
opening window etc
D
Below a gutter, or sanitary pipework
E
Below the eaves
F
Below a balcony or carport roof
G
Above ground, roof or balcony level
H
From vertical drain/soil pipe work
J
From an internal or external corner
K
From a surface facing a terminal
L
Vertically from a terminal on the same wall
M Horizontally from a terminal on the same wall
N
From a terminal facing the terminal
P
From an opening in a
carport (e.g. door, windows)
into the
building
Q
From adjacent wall to flue (vertical only)
R
From internal corner to flue (vertical only)
S
Below eaves or balcony (vertical only)
Terminal Position with Minimum Distance (mm)
Note: The distance from a fanned draught appliance terminal installed
parallel to a boundary may not be less than 300 mm in accordance with
the diagram on the left.
300
300
300
75
200
200
300
150
300
600
1500
300
1200
1200
210
230
600
Top View Rear Flue
Top View Side Flue
Terminal
Assembly
Property Boundary Line
Fanned Draught
Fanned Draught
300 min.
300 min.
FLU0005A
Reduced Clearances
This range of boilers has been tested and approved for use with certain
clearances less than those shown above.
Only one of these reductions may be used on a single installation.
RSL40-70
RSL80-100
D
Below a gutter, or sanitary pipework
25
25
E
Below the eaves
25
25
F
Below a balcony or carport roof
25
25
H
From vertical drain/soil pipe work
25
---
J
From an internal or external corner
25
---
Summary of Contents for Kingfisher Mf CFL40 - 100
Page 13: ...Publication No 5102977 13 CON0093B Installation Requirements Fig 8 Fig 7 ...
Page 14: ...Publication No 5102977 14 Installation Requirements Fig 9 Fig 10 ...
Page 31: ...Publication No 5102977 31 Fig 30 Pictorial Wiring Diagram CON0082B T T B CFL Models Only ...
Page 34: ...Publication No 5102977 34 Fault Finding ...