28
External Wiring
WARNING: All external ports should be equipped with switches.
CAUTION: All cables shall be connected in sequence as listed in this manual.
NOTE: The actual connection depends on your application case. Not all the ports
are necessary to be connected.
(1)
Refer to the table below for minimum copper wire sizing and ratings.
Voltage
Rating
Temp.
Class
Gauge
AC/Ground
600V
75°C
8AWG (8.37mm2)
PV/Battery
600V
75°C
10AWG (5.26mm2)
12Vdc/AFCI
Communication
30V
60°C
24AWG (0.204mm2)
Ethernet
30V
60°C
Standard Ethernet cable
(2)
Refer to the table below for minimum external switch sizing and ratings
Voltage
Rating
Current Rating
AC
600V
63A
PV
600V
30A
(3)
Connect Universal PCS to ground.
CAUTION: As the inverter is transformer-free, neither positive nor negative
polarities of PV arrays shall be ground connected; otherwise, it may present
a risk of inverter failure. In a photovoltaic energy system, all metal
components that are non-current-carrying, e.g. brackets, combiner boxes,
distribution boxes, inverter boxes, shall be grounded.