Failure in CAN communication. Reconnect communication cable between
BCMS and battery module, then reboot
the system.
(11)
The Status Indicator on BCMS module/battery system/battery module is
solid yellow while SOC is 0%.
Low battery
Charge the battery.
(12)
The Run Indicator on Universal PCS is solid red.
Inverter unit fault, including
overload, short circuit, grid
over voltage, overfrequency,
etc.
Check if the load is abnormal. Reboot
Universal PCS. If it does not recover, shut
it down and contact us.
Abnormal connection/voltage
of batteries
Check battery connection and battery
voltage. Reboot Universal PCS. If it does
not recover, shut it down and contact us.
(13)
The Run Indicator on Universal PCS is solid yellow.
PV charging unit fault, e.g., PV
input over-voltage
Check PV input voltage. Reboot Universal
PCS. If it does not recover, shut it down
and contact us.
Abnormal connection/voltage
of batteries
Check battery connection and voltage.
Reboot Universal PCS. If it does not
recover, shut it down and contact us.
(14)
The Run Indicator on Universal PCS is blinking green, and the Status
Indicator on Universal PCS is blinking blue.
Inverter unit/PV charging unit
is upgrading.
Wait until upgrade is finished. If the
blinking blue keeps, reboot Universal PCS.
If it does not recover, shut it down and
contact us.
(15)
The Status Indicator on Universal PCS is blinking red.
Communication fault between
energy management unit and
battery system
Reboot Universal PCS, then reboot battery
system. If it is not recovered, shut it down
and contact us.