46
(3)
Put all the covers back on the unit and screw tightly (Torque: 1.2 N·m).
Safety Check
DANGER: Check thoroughly, all operations in the installation, ensuring the
system is installed correctly. Pay special attention that DC and AC voltages
are in the specified ranges of iCAN NetZero Plus.
Items
Notes
PV connection
External breaker is installed.
The appropriate breaker is installed as specified.
The breaker is switched OFF.
Open-circuit voltage of PV arrays is lower than
450V.
Positive and negative polarities are correct.
Battery connection
There is no voltage to the battery interfaces.
Positive, negative, and REF polarities are correct.
AC breaker
AC breaker is turned OFF.