background image

Pre-installation requirements

The sub floor must be swept clean and be free from mortar residues.

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Installation

Fitting Insulation 

Step 1:

In accordance with Part ‘L’ of the current Building Regulations, 
a suitable layer of insulation material should be included within 
the floor construction. It is the responsibility of the Architect or 
Builder to ensure compliance. However, in all instances insulation 
must be installed beneath the under floor heating system in order 
to ensure that any downward heat loss does not exceed 10W/m

2

in accordance with BS EN 1264.

Fitting the edge insulation strips 

Step 2:

Using edge insulation strip allows the free expansion of the floor 
screed. The insulation strip should be installed around all perimeter 
walls and fixed constructions such as columns, steps and access doors.

Edge insulation strip is bent at 90° near to the base to form 
a double sided self-adhesive strip which bonds the floor plates 
to the floor insulation. Edge insulation strip should be fitted in 
addition to perimeter insulation required by Building Regulations.

Fitting the floor panels 

Step 3:

The floor panels are laid over the pre-installed insulation and 
should be overlapped at the edges.

 

 
 
 
 

NOTE:

 The ½ castellation should overlap the ¾ castellation. The first 

panel should be laid with the ½ castellation edge against the wall. 

Panels can be cut by simply using a saw or snips or it can 
be overlapped to the nearest castellation fit.

Floor panels should not be used at the base of the manifold 
as pipes need to be closer together than the floor panels allow. 
Pipes around this area should be secured using pipe clips which can 
also be used intermittently to secure the clip plate to the insulation.

When a pumped (liquid) screed is to be used it is essential that all of 
the panel joints are made correctly and that no panels are allowed to 
simply ‘butt-up’ as this may allow the screed to penetrate below the 
under floor heating system and cause the panels to rise up. Similarly 
the panels should be firmly secured around the perimeter of the room 
using staples so as to prevent possible risk of the panels lifting.

Preparing the pipe 

Step 4:

You will need to remove the coil from the bag, leaving the shrink 
wrap on, uncoiling from centre of the coil.

Laying the pipe 

Step 5:

Once you have completed laying the solid floor panels the pipe 
can be fitted starting at the manifold position in line with the 
pre-designed centres. 15mm and 18mm pipe can be laid 
at 100mm or 200mm centres as required, 18mm pipe can also 
be laid at 300mm centres.

The minimum bend radius is achieved by encircling two 
castellations for a 90° bend or three castellations for a 180° bend 
(see diagrams on next page).

12

13

SOLID FLOOR

Key design and installation information

Material requirements (approx)

Maximum heat output 

Approx.

 

100W/m

2

Recommended design flow temp 

50°C

Maximum circuit length 

100m (15mm pipe) 

 

120m (18mm pipe)

Maximum coverage per circuit 

12m

2

 at 100mm centres

 

22m

2

 at 200mm centres 

 

30m

2

 at 300mm centres* 

 

*(18mm pipe only)

Pipe 

8.2m/m

2

 at 100mm centres

 

4.5m/m

2

 at 200mm centres

 

3.3m/m

2

 at 300mm spacing* 

 

*(18mm pipe only)

Floor plate usage 

1 plate/m

2

 allowing 

 

for cutting 

 

(Actual 1·2m

2

/plate)

Edging insulation strip 

1.1m/m

2

Conduit pipe 

2m/circuit

Polypipe under floor heating in solid or screeded floors incorporates the unique 

Polypipe screeded floor panel. The lightweight plastic floor panels nest 

for easy storage and carrying.

Polypipe has the perfect solution for installing under floor 
heating into solid or screeded floors. Utilising our unique 
lightweight plastic floor panels, which are quick and easy to 
cut to size, it is possible to fit Polypipe under floor heating into 
any shaped room.

Polypipe solid floor panels form a simple grid to ensure the 
fastest possible pipe laying and also provide a precise guide 
for the pipe, ensuring that the minimum pipe bending 
radius is achieved. 

The panels are laid above pre-installed insulation and the 
system includes edging insulation strip to ensure maximum 
performance and efficiency.

Polypipe under floor heating systems can be used with 
the following solid floor constructions:

  Sand & cement screed (4:1 mix) 

  Pumped screed systems (anhydrite, etc) 

  Fine or heavy concrete 

  Polymer modified screeds

Summary of Contents for Under Floor Heating Systems

Page 1: ...s Broomhouse Lane Edlington Doncaster DN12 1ES Tel 01709 770 000 Fax 01709 770 001 2410 London Road Mount Vernon Glasgow G32 8XZ Tel 0141 778 8822 Fax 0141 778 2703 Dromore Road Lurgan Craigavon Co Ar...

Page 2: ...revious printed copies will become out of date The latest version of our installation advice including a downloadable version of the current Technical Installation Guide can be found at our trade webs...

Page 3: ...xtensive back up service Technical representation available to discuss systems in general and particular projects www ufch com Technical Installation CD Specialist Technical Hotline on 01709 770000 En...

Page 4: ...he floor screed is required by Building Regulations Edge insulation also acts as an expansion joint Floating Floor When installed in floating floors Polyplumb pipe is simply pressed in to the pre form...

Page 5: ...r requires a bespoke design You then simply input data for each room providing floor type room size and control zones to calculate the required pack All packs have a single order code and include all...

Page 6: ...h when heated will reduce to 8 9 and cause only a very small amount of shrinkage The floor will re absorb some moisture when the heating is not operating and the moisture content will increase to 12 1...

Page 7: ...d around the perimeter of the room using staples so as to prevent possible risk of the panels lifting Preparing the pipe Step 4 You will need to remove the coil from the bag leaving the shrink wrap on...

Page 8: ...ted the screed cover can be applied Care should be taken to ensure that the screed is tightly compacted around the pipe to ensure that no voids are present The system should remain under pressure 6 ba...

Page 9: ...nder pressure whilst the flooring is laid Finishing The room can then be finished by fitting 18mm or 22mm tongue and groove sheets of chipboard glued on the edge over the floating floor system Mark th...

Page 10: ...hed downwards and away from the underside of the timber finished floor covering as this could lead to potential underperformance of the system Testing Step 4 Once the pipe circuits have been installed...

Page 11: ...These can be fixed directly through the spreader plate down in to the joists below It is important to indicate the position of pipework in areas where the additional fixing of items such as carpet gri...

Page 12: ...heir high output at relatively low flow temperatures Modular Heating Panels are ideal for maximising heat efficiency and lowering energy consumption In most installations it is not necessary to cover...

Page 13: ...should be selected The span is defined as the free space from wall to wall that needs to remain uninterrupted by trimmers or other services Ideally install MHP panels prior to other services whenever...

Page 14: ...omes into direct contact with it Always ensure that electrical cables are not in physical contact with the MHP panels using tape or a polythene strip Finishing Once you have connected your system up t...

Page 15: ...for heavyweight floor coverings such as ceramics or where the floor covering needs to be secured directly to the panel e g solid wood Overlay Lite is a high compressive strength lightweight insulated...

Page 16: ...is should be the first consideration for most projects The more structural nature of Overlay however makes it ideal for direct tiling or application of floor finishes which need to be fixed or screwed...

Page 17: ...mple of blanking in a bathroom Example of squaring off an irregular room plan Room layouts The following diagrams show some examples of room shapes pipe requirements and interruptions pillars hearths...

Page 18: ...wood floors they can be discretely screwed through the tongue and groove directly into the Overlay panel avoiding pipe circuitry to minimise movement in the floor covering If over boarding with 6mm p...

Page 19: ...r covering as normal It is advisable to mark out pipe positioning to avoid stapling pipes when fitting carpets 36 37 Overlay Lite for lightweight floor coverings Installation Laying end returns Step 1...

Page 20: ...stic hot water primary circuits To provide independent hydraulic control of the entire system it is important that the installation is designed as an S Plan or S Plan Plus configuration which allows f...

Page 21: ...d in under floor heating systems is less than that required for radiators or stored hot water If these other services are connected to the same boiler it will be necessary to control the water tempera...

Page 22: ...iring centre and slave units Available in two surface finishes and offers the following features Large touch screen display with high visibility blue LED backlight On screen display shows current stat...

Page 23: ...distribution pipe work Connection from nearest radiator 260mm 200mm Pump Pipe thermostat Heating return Heating flow Under floor heating flow Under floor heating return Thermostatic blending valve Pu...

Page 24: ...ible tap connectors for the simplest method of connection Close all under floor heating circuits except one by screwing down the blue caps and closing the isolating valves situated on top of the manif...

Page 25: ...resistant to the build up of scale Short term chlorination for disinfection of supply pipe work and normal levels of chlorine in UK domestic water supplies will not have an adverse effect on the integ...

Page 26: ...ng should be done with all switches on and room thermostats calling Fault finding complete Adjust pump speed and set flow rates in accordance with the system design data as provided NO NO Is the boile...

Page 27: ...Manufacturing quality assurance In accordance with BS ES ISO 9001 2000 BSI registered firm Certificate FM00318 Installation standard To follow the recommendations of BS5955 Part 8 2001 Plastic Pipewo...

Page 28: ...OR HEATING REQUIREMENTS Manifold Position s Please also indicate on drawing Floor Type Solid Suspended Floating MHP Overlay Overlay Lite Ground Floor 1st Floor 2nd Floor CONSTRUCTION DETAILS If NOT to...

Reviews: