background image

Pre-installation requirements

The sub floor must be swept clean and be free from mortar residues.

Installation

Laying the floating floor panels 

Step 1:

Lay the 1200 x 1200 x 50mm floating floor panels directly over 
the entire floor area to be heated, ensuring the panel grooves are 
aligned. The panels can be cut to fit where necessary.

 
 
 
 
 
 
 
 
 
A void in the insulation is often retained around the edge of the 
room to allow for distribution pipes to be laid from the room 
to the manifold.

 

 

 

 
Laying the spreader plates 

Step 2:

Single heat spreader plates that have pre-formed grooves at 
300mm centres need to be laid on top of the floating floor panels. 
These plates ensure an even spread of heat across the floor area 
and hold the pipe firmly within place in the floating floor panel.

Laying the pipe 

Step 3:

Once you have completed laying the floating floor panels and heat 
spreader plates the pipe can be fitted into the pre-formed grooves of 
the heat spreader plate. Start at the manifold position and use the 
grooves in the floating floor panel to loop round the entire room.

The maximum circuit length is 80m using 15mm pipe or 100m 
using 18mm pipe. Pipe should be laid in the pattern shown below.

 
 

 

NOTE: 

Areas of potential high point loading, e.g. under heavy 

furniture kitchen units and appliances, will require additional floor 
support. Timber battens (50mm x 50mm) should be positioned 
between the floating floor panels and notched to allow the passage 
of pipes.

Testing 

Step 4:

Once the pipe circuits have been installed and connected to the 
manifold the system should be pressure tested to 6 bar for a 
minimum of 1 hour before the timber floor covering is laid. It is 
recommended that the system remains under pressure whilst the 
flooring is laid.

 

Finishing

The room can then be finished by fitting 18mm or 22mm tongue and 
groove sheets of chipboard, glued on the edge, over the floating floor 
system. Mark the position of the pipe where door thresholds or carpet 
strip are to be installed. 

When laying a ceramic or stone floor covering ensure that any 
deflection in the floor is minimised. It is recommended that a slip mat 
or uncoupling membrane is used rather than a second layer of wood.

The Polypipe floating floor system is designed for use in applications where a solid 

floor installation is not suitable due to structural weight limitations or where a 

‘dry build’ floor option is required. Suitable for use in either new build or existing 

properties, the floating floor panels can be installed directly on top of both solid 

and timber floors.

The 50mm thick high density polystyrene panels have a 
thermal value of 0.036W/mK and can be used to enhance 
the thermal insulation requirement of the floor structure as 
required under current Building Regulations. However, care 
should be taken when installing floating floor panels on top 
of a primary insulation layer to ensure that excessive deflection 
does not occur in the final floor construction.

It is therefore recommended that any other insulation 
materials used below the floating floor panels are of a high 
density construction (100kN/m

2

 @ 10% compression min).

16

17

FLOATING FLOOR

Key design and installation information

Pipe 

3.1m/m

2

 at 300mm centres

Floating floor panel 

1 panel/1.4m

2

Single spreader plate 

3 plates/m

2

Material requirements (approx)

Maximum heat output 

Approx.

 

70W/m

2

Recommended design flow temp 

60°C

Maximum circuit length 

80m (15mm pipe) 

 

100m (18mm pipe)

Maximum coverage per circuit 

25.8m

2

 at 300mm centres  

 

(15mm pipe)

 

30m

2

 at 300mm centres  

 

(18mm pipe)

Polyplumb

barrier pipe

Single heat

spreader plate

Insulated floating 

floor panel

Summary of Contents for Under Floor Heating Systems

Page 1: ...s Broomhouse Lane Edlington Doncaster DN12 1ES Tel 01709 770 000 Fax 01709 770 001 2410 London Road Mount Vernon Glasgow G32 8XZ Tel 0141 778 8822 Fax 0141 778 2703 Dromore Road Lurgan Craigavon Co Ar...

Page 2: ...revious printed copies will become out of date The latest version of our installation advice including a downloadable version of the current Technical Installation Guide can be found at our trade webs...

Page 3: ...xtensive back up service Technical representation available to discuss systems in general and particular projects www ufch com Technical Installation CD Specialist Technical Hotline on 01709 770000 En...

Page 4: ...he floor screed is required by Building Regulations Edge insulation also acts as an expansion joint Floating Floor When installed in floating floors Polyplumb pipe is simply pressed in to the pre form...

Page 5: ...r requires a bespoke design You then simply input data for each room providing floor type room size and control zones to calculate the required pack All packs have a single order code and include all...

Page 6: ...h when heated will reduce to 8 9 and cause only a very small amount of shrinkage The floor will re absorb some moisture when the heating is not operating and the moisture content will increase to 12 1...

Page 7: ...d around the perimeter of the room using staples so as to prevent possible risk of the panels lifting Preparing the pipe Step 4 You will need to remove the coil from the bag leaving the shrink wrap on...

Page 8: ...ted the screed cover can be applied Care should be taken to ensure that the screed is tightly compacted around the pipe to ensure that no voids are present The system should remain under pressure 6 ba...

Page 9: ...nder pressure whilst the flooring is laid Finishing The room can then be finished by fitting 18mm or 22mm tongue and groove sheets of chipboard glued on the edge over the floating floor system Mark th...

Page 10: ...hed downwards and away from the underside of the timber finished floor covering as this could lead to potential underperformance of the system Testing Step 4 Once the pipe circuits have been installed...

Page 11: ...These can be fixed directly through the spreader plate down in to the joists below It is important to indicate the position of pipework in areas where the additional fixing of items such as carpet gri...

Page 12: ...heir high output at relatively low flow temperatures Modular Heating Panels are ideal for maximising heat efficiency and lowering energy consumption In most installations it is not necessary to cover...

Page 13: ...should be selected The span is defined as the free space from wall to wall that needs to remain uninterrupted by trimmers or other services Ideally install MHP panels prior to other services whenever...

Page 14: ...omes into direct contact with it Always ensure that electrical cables are not in physical contact with the MHP panels using tape or a polythene strip Finishing Once you have connected your system up t...

Page 15: ...for heavyweight floor coverings such as ceramics or where the floor covering needs to be secured directly to the panel e g solid wood Overlay Lite is a high compressive strength lightweight insulated...

Page 16: ...is should be the first consideration for most projects The more structural nature of Overlay however makes it ideal for direct tiling or application of floor finishes which need to be fixed or screwed...

Page 17: ...mple of blanking in a bathroom Example of squaring off an irregular room plan Room layouts The following diagrams show some examples of room shapes pipe requirements and interruptions pillars hearths...

Page 18: ...wood floors they can be discretely screwed through the tongue and groove directly into the Overlay panel avoiding pipe circuitry to minimise movement in the floor covering If over boarding with 6mm p...

Page 19: ...r covering as normal It is advisable to mark out pipe positioning to avoid stapling pipes when fitting carpets 36 37 Overlay Lite for lightweight floor coverings Installation Laying end returns Step 1...

Page 20: ...stic hot water primary circuits To provide independent hydraulic control of the entire system it is important that the installation is designed as an S Plan or S Plan Plus configuration which allows f...

Page 21: ...d in under floor heating systems is less than that required for radiators or stored hot water If these other services are connected to the same boiler it will be necessary to control the water tempera...

Page 22: ...iring centre and slave units Available in two surface finishes and offers the following features Large touch screen display with high visibility blue LED backlight On screen display shows current stat...

Page 23: ...distribution pipe work Connection from nearest radiator 260mm 200mm Pump Pipe thermostat Heating return Heating flow Under floor heating flow Under floor heating return Thermostatic blending valve Pu...

Page 24: ...ible tap connectors for the simplest method of connection Close all under floor heating circuits except one by screwing down the blue caps and closing the isolating valves situated on top of the manif...

Page 25: ...resistant to the build up of scale Short term chlorination for disinfection of supply pipe work and normal levels of chlorine in UK domestic water supplies will not have an adverse effect on the integ...

Page 26: ...ng should be done with all switches on and room thermostats calling Fault finding complete Adjust pump speed and set flow rates in accordance with the system design data as provided NO NO Is the boile...

Page 27: ...Manufacturing quality assurance In accordance with BS ES ISO 9001 2000 BSI registered firm Certificate FM00318 Installation standard To follow the recommendations of BS5955 Part 8 2001 Plastic Pipewo...

Page 28: ...OR HEATING REQUIREMENTS Manifold Position s Please also indicate on drawing Floor Type Solid Suspended Floating MHP Overlay Overlay Lite Ground Floor 1st Floor 2nd Floor CONSTRUCTION DETAILS If NOT to...

Reviews: