Functional Description and Specifications RUB SW
2.6.3
Alarms by SNMP Traps
SNMP functionality for a RUBIDIUM system requires the installation of an Ethernet module
(
RUB IE
or
RUB PM
) with option
S
(SNMP).
Utilizing one of the configuration tools, the SNMP traps can be enabled and disabled at the
System
page (please refer to chapter
‘
”
System
”
: Identification, Reset, SNMP, Fan Control
’
).
The “Any Trap” checkbox in genera
l controls the SNMP traps functionality. Furthermore, there
are checkboxes corresponding to all the individual traps.
Recommen
ded configuration: Check the “Any Trap” and “System Failure” checkboxes.
This chapter describes all the alarm functions for traps. The following feature is valid for all
these traps: As long as the alarm condition is present, traps will be repeated in an 8 hours
interval.
Signal 1 Failure / Signal 2 Failure
Check the “Signal Failure“ checkbox
Trap will be sent as long as there is any major word clock error at
CLOCK IN 1
or
CLOCK IN 2
respectively. In detail, this trap will be sent if one of the following errors has
occurred and this error has been enabled to indicate a failure (checkbox “
disable
“
not
checked):
signal loss
frequency
signal to pps drift
Please refer to chapter
‘
Word Clock Monitoring
’
for a detailed error description.
Word Clock Warning
Check t
he “Signal Warning“ checkbox
Trap will be sent in case of an error at a word clock signal pair. In detail, this trap will be
sent if one of the following errors has occurred and this error has been enabled to
indicate a failure (checkbox “
disable
“
not checked):
word clock frequency difference
word clock signal to signal drift
Please refer to chapter
‘
Word Clock Monitoring
’
for a detailed error description.
System Warning
Check the “Signal Warning“ checkbox
In detail, this trap will be sent if one of the following errors has occurred and this error
has been enabled to indicate a failure (checkbox “
disable
“
not checked):
pps timeout
(real-time ref.)
serial timing
(real-time ref.)
power on
(self test)
pps timing
(real-time ref.)
serial sequence
(real-time ref.)
relays
(self test)
Please refer to chapter ‘
Real Time Reference Monitoring
’
and chapter
‘
Self Test
’
.
System Error
Check the “System Error“ checkbox
Active, as long as the “
overall errors
” counter has a count value > 0.
The error indication cannot be disabled, so this trap will be sent in case of any error, i.e.
word clock/real-time reference/self test errors.
System Failure
Check th
e “System Failure“ checkbox
Active, as long as the “
overall failures
” counter has a count value > 0.
Any individual errors can raise this alarm provided this error has been enabled to
indicate a failure (checkbox “
disable
“
not checked). Depending on this configuration,
word clock/real-time reference/self test errors may activate this trap.