A 15 amp, 120 Volt, 60 Hz circuit with a properly grounded outlet is required. Preferably, the fireplace will
be on a dedicated circuit as other appliances on the same circuit may cause the circuit breaker to trip
or the fuse to blow when the heater is in operation. The unit comes standard with a 6 ft. (1.8 m) long three
wire cord, exiting the right side of the fireplace. Plan the installation to avoid the use of an extension cord.
Extension cords are for temporary use only. If an extension cord must be used, it must be UL/CSA certified,
rated at 15A (1875W), 125V maximum with 14 AWG minimum and constructed of two current carrying conductors
with ground. A heavy duty extension cord with the shortest length possible for the connection is recommended
and must not be longer than 50 ft. (15.2 m). Do not coil or cover the extension cord.
Electrical outlet wiring must comply with local building codes and other
applicable regulations to reduce the risk of fire, electrical shock
and injury to persons.
Do not use this fireplace if any part of it has been under water.
Immediately call a qualified service technician to inspect the fireplace
and replace any part of the electrical system which has been under water.
4
This heater is for use on 120 volts. The cord has a plug as shown at (A) in Figure 1. An adapter as shown at (C)
is available in the USA only for connecting three-blade grounding-type plugs to two-slot receptacles. The green
grounding lug extending from the adapter must be connected to a permanent ground such as a properly grounded outlet
box. The adapter should not be used if a three-slot grounded receptacle is available. NOTE: Adapters are NOT for
use in Canada.
Electrical Connection
Grounding Instructions
Electric Fireplace Insert 18/
23
GROUNDING
PIN
METAL SCREW
GROUNDING
MEANS
COVER OF GROUNDED
OUTLET BOX
ADAPTER
(A)
(B)
(C)
(D)
Figure 1
GROUNDING
PIN