22 -
STR561 - User manual
7.8
Customizable linearisation of analogue input
Selecting
16 steps
on parameter 17
V/I custom
and connecting a linear sensor
it is possible to customize the linear input for a max. of 16 steps. On parameters
xx-Input value
it is necessary to enter the value of the input to which the value
selected on the corresponding parameter
xx-Custom value
will be related.
EExample: sensor 0-5V.
01-Input value=> 0.000V
01-Custom value=>0mBar
02-Input value => 2.000V
02-Custom value=>100mBar
03-Input value => 4.000V
03-Custom value=>500mBar
04-Input value => 5.000V
04-Custom value.=>1000mBar
At each value in Volt (input) a value in mBar (customized) is related: if the sensor
supplies 2V the device visualizes 100mBar, if it supplies 4V the device visualizes
500mBar. For intermediate tension values the value in mBar is calculated
linearly
between the entered values containing it: 1V = 50mBar, 3V=300mBar
and 4,5V=750mBar.
8
Alarm Intervention Modes
8.a
Absolute alarm (absolute selection)
1
Alarm Spv
Pv
Off
On
On
Off
Hysteresis
par. > 0
Time
Alarm
output
Absolute alarm and hysteresis value
greater than “0” (Parameter 58
hysteresis
> 0).
N.B. The example refers to alarm 1;
the function can also be enabled for
alarms 2