12 -
STR561 - User manual
5.1.e
Relay Q2 output
Q2
1
2
2A 230V
Resistive
1/8HP
Contacts capacity: 2A/250 Vac for resistive loads.
NB
: see picture below
Electrical endurance Q1 / Q2.
2 A, 250 Vac, resistive load, 10
5
operations.
20/2 A, 250 Vac, cosφ = 0.3, 10
5
operations.
5.1.f
Output AO1 mA
AO1
0/4..20mA
9
8
Pins 8-9
: analogue output in
mA
configurable by
parameters as retransmission of process or alarm setpoints
(see parameters 112-116).
5.1.g
Digital Input 1
+12 V DC
DI.1
(PnP)
10
11
PNP digital input.
Digital input configurable by parameter 95
Short-circuit pins 10 and 11 to activate digital input 1
.