Make sure that the tubing and line accessories are in good condition.
Diesel fuel leaks can damage objects and injure persons.
-
Never start or stop the pump by inserting or removing any plugs.
-
Do not operate switches with wet hands.
-
Prolonged contact with Diesel fuel can damage the skin. The use of
glasses and gloves is recommended.
-
Motors are provided with an automatic thermal protection switch.
-
Extreme operating conditions can raise the motor temperature and,
consequently, cause the thermal protection switch to stop it. Turn off
the pump and wait for it to cool before resuming use. The thermal
protection automatically turns off when the motor is sufficiently cool.
The motors are not of an anti-explosive type.
DO NOT install them where inflammable vapors could be present.
I2
START UP OPERATIONS AND DAILY USE
-
Attach the ends of the tubing to the tanks. In the absence of an
appropriate slot, solidly grasp the delivery tube before beginning the
cleaning operation.
-
Before starting the pump make sure that the delivery tube is attached to
the tank.
-
Turn the ON/OFF switch of the motor to ON and start cleaning the oil. The
by-pass valve allows functioning with the delivery closed for only brief
periods.
-
Check the pressure indicated by the pressure gauge on the filter cover.
When the indication exceeds 5 bars, the filter must be replaced in order to
avoid a motor overload, caused by the high filtration resistance.
I3
LACK OF ELECTRIC POWER
A lack of electric power, with the consequent accidental stopping of the
pump, can be caused by:
-
A safety device tripping
-
A drop in line voltage
In either case, act as follows: