background image

Installation Precautions

 – 

Adherence to the following will aid in problem-free installation with long-term reliability:

WARNING

 - 

Several different sources of power can be connected to 

the fire alarm control panel.

  Disconnect all sources of power before 

servicing.  Control unit and associated equipment may be damaged by 

removing and/or inserting cards, modules, or interconnecting cables 

while the unit is energized.  Do not attempt to install, service, or 

operate this unit until this manual is read and understood.

CAUTION 

System Reacceptance Test after Software Changes: 

To 

ensure proper system operation, this product  must be tested in 

accordance with NFPA 72-1993 Chapter 7 after any programming 

operation or change in site-specific software.  Reacceptance testing is 

required after any change, addition or deletion of system components, 

or after any modification, repair or adjustment to system hardware or 

wiring.
All components, circuits, system operations or software functions 

known to be affected by a change must be 100% tested.  In addition, to 

ensure that other operations are not inadvertently affected, at least 

10% of initiating devices that are not directly affected by the change, 

up to a maximum of 50 devices must also be tested and proper system 

operation verified.

This system

 meets NFPA requirements for operation at 0-49

O

C/

32-120

O

 F and at a relative humidity of 85% RH (non-condensing) at 

30

O

C/86

O

 F.  However, the useful life of the system's standby batteries 

and the electronic components may be adversely affected by extreme 

temperature ranges and humidity.  Therefore, it is recommended that 

this system and its peripherals be installed in an environment with a 
nominal room temperature of 15-27

O

C/60-80

O

 F.

Verify that wire sizes are adequate

 for all initiating device loops.  

Most devices cannot tolerate more than a 10% I.R. drop from the 

specified device voltage.

Like all solid state electronic devices

, this system may operate 

erratically or can be damaged when subjected to lightning induced 

transients.  Although no system is completely immune from lightning 

transients and interferences, proper grounding will reduce 

susceptibility.  

Overhead or outside aerial wiring is not recommended, 

due to an increased susceptibility to nearby lightning strikes.

  Consult 

with the Technical Services Department if any problems are 

anticipated or encountered.

Disconnect AC power and batteries 

prior to removing or inserting 

circuit boards.  Failure to do so can damage circuits.

Remove all electronic assemblies 

prior to any drilling, filing, reaming 

or punching of the enclosure.  When possible, make all cable entries 

from the sides or rear.  Before making modifications, verify that they 

will not interfere with battery, transformer and printed circuit board 

location.

Do not tighten screw terminals

 more than 9 in-lbs.  Over tightening 

may damage threads, resulting in reduced terminal contact pressure 

and difficulty with screw terminal removal.

This system

 contains static-sensitive components  Always ground 

yourself with a proper wrist strap before handling any circuits so that 

static charges are removed from the body.  Use static suppressive 

packaging to protect electronic assemblies removed from the unit.

Follow the instructions

 in the installation, operating and 

programming manuals.  These instructions must be followed to avoid 

damage to the control panel and associated equipment.  FACP 

operation and reliability depend upon proper installation.

Fire Alarm System Limitations

An automatic fire alarm system 

- typically made up of smoke 

detectors, heat detectors, manual pull stations, audible warning 

devices and a fire alarm control with remote notification capability can 

provide early warning of a developing fire.  Such a system, however, 

does not assure protection against property damage or loss of life 

resulting from a fire.

Any fire alarm system may fail for a variety of reasons:
Smoke detectors

 may not sense fire where smoke cannot reach the 

detectors such as in chimneys, in walls, or roofs, or on the other side of 

closed doors.  Smoke detectors also may not sense a fire on another 

evel or floor of a building.  A second floor detector, for example, may 

not sense a first floor or basement fire.  Furthermore, all types of 

smoke detectors - both ionization and photoelectric types, have 

sensing limitations.  No type of smoke detector can sense every kind of 

fire caused by carelessness and safety hazards like smoking in bed, 

violent explosions, escaping gas, improper storage of flammable 

materials, overloaded electrical circuits, children playing with matches, 

or arson.

IMPORTANT! 

Smoke detectors

 must be installed in the same room 

as the control panel and in rooms used by the system for the 
connection of alarm transmission wiring, communications, signaling 
and /or power.

  If detectors are not so located, a developing fire may 

damage the alarm system, crippling its ability to report a fire.

Audible warning devices

 such as bells may not alert people if these 

devices are located on the other side of closed or partly open doors or 

are located on another floor of a building.

A fire alarm system will

 not operate without any electrical power.  If 

AC power fails, the system will operate from standby batteries only for 

a specified time.

Rate-of-Rise heat detectors

 may be subject to reduced sensitivity 

over time.  For this reason, the rate-of-rise feature of each detector 

should be tested at least once per year by a qualified fire protection 

specialist.

Equipment used in the system 

may not be technically compatible 

with the control panel.  It is essential to use only equipment listed for 

service with your control panel.
T

elephone lines

 needed to transmit alarm signals from a premise to a 

central monitoring station may be out of service or temporarily 

disabled.

The most common cause

 of fire alarm malfunctions, however, is 

inadequate maintenance.  All devices and system wiring should be 

tested and maintained by professional fire alarm installers following 

written procedures supplies with each device.  System inspection and 

testing should be scheduled monthly or as required by National and/or 

local fire codes.  Adequate written records of all inspections should be 

kept.

FCC Warning

WARNING:

 This equipment generates, uses and can radiate radio 

frequency energy and if not installed and used in accordance with the 

nstruction manual, may cause interference to radio communications,  

It has been tested and found to comply with the limits for class A 

computing device pursuant to Subpart B of 15 of FCC Rules, which is 

designed to provide reasonable protection against such interference 

when operated in a commercial environment.  Operation of this 

equipment in a residential area is likely to cause interference, in which 

case the user will be required to correct the interference at his own 

expense.

Canadian Requirements

This digital apparatus does not exceed the Class A limits for radiation 

noise emissions from digital apparatus set out in the Radio 

Interference Regulations of the Canadian Department of 

Communications.
Le present appareil numerique n'emet pas de bruits radioelectriques 

depassant les limites applicables aux appareils numeriques de la 

classe A prescrites dans le Reglement sur le brouillage radioelectrique 

edicte par le ministere des Communications du Canada.

While installing a fire alarm system may make lower insurance 
rates possible, it is not a substitute for fire insurance!

Summary of Contents for NOTIFIER CBC-CLASS 1

Page 1: ...CBC CLASS 1 2 Chicago Building Code Class I Class II Master Control Manual 12 Clintonville Road Northford CT 06472 203 484 7161 203 484 7118 Fax Document 50685 7 09 98 Revision C PN 50685 C ECN 98 303 ...

Page 2: ...vices and a fire alarm control with remote notification capability can provide early warning of a developing fire Such a system however does not assure protection against property damage or loss of life resulting from a fire Any fire alarm system may fail for a variety of reasons Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys in walls or roofs or on t...

Page 3: ...e Cabinet 7 Figure 8 Cabinet Mounting 7 Mounting the Remote Bell Supervision Module 7 Figure 9 Remote Module Mounting 7 Connecting the Master Control 8 Primary Source Connections 8 Figure 10 Source of Energy Module to Main Power Supply Connection 8 Master Control to NOTIFIER FACP Connections 8 Figure 11 Connecting the CBC Master Control System 5000 MPS 24A Annunciator and FCPS 24 9 Figure 12 Conne...

Page 4: ...n be ordered with all the modules ready mounted in a metal cabinet Figure 1 The System Trouble and or City Tie Disconnect Bell Supervision Modules can also be ordered separately for remote mounting The following equipment is required for use with the CBC CLASS 1 2 to comply with the non high rise Class I and Class II type requirements An FCPS 24 Field Charging Power Supply or APS 6R Power Supply A...

Page 5: ...quirements are 24VDC 60 mA The bell power requirements are 24VDC with current dependent upon the make and model of the bell City Tie Disconnect Module Lamp power requirements are 24VDC 60 mA The Module Descriptions section of this manual describes these modules in more detail Compatibility The CBC Master Control can be used in conjunction with the following NOTIFIER fire panels System 5000 Fire Co...

Page 6: ...re 3 Source of Energy Module CBC BSM Chicago Building Code Bell Supervision Module There are two CBC BSM modules One provides the connection for the remote Trouble bell This module may be mounted in the master control cabinet or it may be mounted in a remote location It provides the capability of testing the bell and silencing the bell after a Trouble condition occurs A red incandescent lamp light...

Page 7: ...alarm control panel It consists of a disconnect switch operated by a two pole caption key operated switch and a white incandescent lamp that indicates when the city tie has been disconnected Once the switch has been activated by turning the key the key can not be removed from the lock until the city tie disconnect switch is again placed in the connect position A Trouble condition at the panel may ...

Page 8: ...g Module Mounting and CBC KIT When the System Trouble Bell Supervision Module is ordered as a remote module it comes with a faceplate suitable for mounting to a 4 square double gang box Figure 7 Remote Mounting The CBC KIT includes the following 12 items shown at left and an Installation Guide Two AFP 200 switch covers Two AFP 200 labels Two AFP 400 switch covers One AFP 400 label Two AM2020 AFP10...

Page 9: ... Press the BELL TEST switch to test the City Tie Disconnect bell 2 The BELL NORMAL SILENCE switch should remain in the NORMAL position until the City Tie Disconnect bell sounds 3 Place the switch in the SILENCE position to silence the City Tie Disconnect Bell The red light labelled BELL SILENCED will go on The red light will remain on until the system BELL SILENCE switch is returned to the NORMAL ...

Page 10: ...upper keyholes mount the backbox over the two screws and tighten Install the lower two fasteners AC power wires should be pulled into the cabinet through a knockout separate from power limited wiring CAUTION Sources of power should be disconnected before installation Power limited wires should be pulled through other knockouts provided Figure 8 Cabinet Mounting Mounting the Remote Bell Supervision...

Page 11: ... Power Supply Connection Master Control to NOTIFIER FACP Connections Figure 11 through Figure 16 specifically illustrate the CBC Master Control connections to each of the compatible NOTIFIER Fire Alarm Control Panels as well as to the graphic annunciator FCPS 24 and APS 6R Before starting review the following notes NOTES CAUTION Turn off the power at the main power distribution panel All sources o...

Page 12: ...FACP Connections Connecting the Master Control CBC CLASS 1 2 Master Control PN 50685 C 7 09 98 9 Figure 11 Connecting the CBC Master Control System 5000 MPS 24A Annunciator and FCPS 24 Note FACP Secondary Power must be installed ...

Page 13: ...aster Control to NOTIFIER FACP Connections 10 CBC CLASS 1 2 Master Control PN 50685 C 7 09 98 Figure 12 Connecting the CBC Master Control to the System 5000 MPS 24B Annunciator and FCPS 24 Note FACP Secondary Power must be installed ...

Page 14: ... FACP Connections Connecting the Master Control CBC CLASS 1 2 Master Control PN 50685 C 7 09 98 11 Figure 13 Connecting the CBC Master Control AFP 200 with RTM 8 Annunciator and APS 6R Note FACP Secondary Power must be installed ...

Page 15: ...rol Master Control to NOTIFIER FACP Connections 12 CBC CLASS 1 2 Master Control PN 50685 C 7 09 98 Figure 14 Connecting the CBC Master Control AFP 200 with 4XTM Annunciator and APS 6R Note FACP Secondary Power must be installed ...

Page 16: ...IFIER FACP Connections Connecting the Master Control CBC CLASS 1 2 Master Control PN 50685 C 7 09 98 13 Figure 15 Connecting the CBC Master Control AFP 400 Annunciator and APS 6R Note FACP Secondary Power must be installed ...

Page 17: ...ster Control to NOTIFIER FACP Connections 14 CBC CLASS 1 2 Master Control PN 50685 C 7 09 98 Figure 16 Connecting the CBC Master Control to the AM2020 AFP1010 MPS 24A Annunciator and APS 6R Note FACP Secondary Power must be installed ...

Page 18: ...Master Control to NOTIFIER FACP Connections Connecting the Master Control CBC CLASS 1 2 Master Control PN 50685 C 7 09 98 15 NOTES ...

Page 19: ...Connecting the Master Control Master Control to NOTIFIER FACP Connections 16 CBC CLASS 1 2 Master Control PN 50685 C 7 09 98 NOTES ...

Page 20: ...ing constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges that NOTIFIER is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience tran...

Reviews: