Sentinel & PimaGuard
Installation Guide 59
TT
Tamper Trouble
Equipment enclosure opened in disarmed state
Zone or point
TU
Tamper Unbypass
Tamper detection bypass has been removed
Zone or point
TW
Area Watch Start
Area watch feature has been activated
Unused
TX
Test Report
An unspecified (manual or automatic) communicator test
Unused
TZ
Area Watch End
Area watch feature has been deactivated
Unused
UA
Untyped Zone Alarm Alarm condition from zone of unknown type
Zone or point
UB
Untyped Zone
Bypass
Zone of unknown type has been bypassed
Zone or point
UG
Unverified Event –
Untyped
A point assigned to a Cross Point group has gone into alarm but
the Cross Point remained normal
Zone or point
UH
Untyped Alarm
Restore
Alarm condition eliminated
Zone or point
UJ
Untyped Trouble
Restore
Trouble condition eliminated
Zone or point
UR
Untyped Zone
Restoral
Alarm/trouble condition eliminated from zone of unknown type
Zone or point
US
Untyped Zone
Supervisory
Unsafe condition from zone of unknown type
Zone or point
UT
Untyped Zone
Trouble
Trouble condition from zone of unknown type
Zone or point
UU
Untyped Zone
Unbypass
Bypass on zone of unknown type has been removed
Zone or point
UX
Undefined
An undefined alarm condition has occurred
Unused
UY
Untyped Missing
Trouble
A point or device which was not armed is now logically missing
Zone or point
UZ
Untyped Missing
Alarm
A point or device which was armed is now logically missing
Zone or point
VI
Printer Paper In
TRANSMITTER or RECEIVER paper in
Printer number
VO
Printer Paper Out
TRANSMITTER or RECEIVER paper out
Printer number
VR
Printer Restore
TRANSMITTER or RECEIVER trouble restored
Printer number
VT
Printer Trouble
TRANSMITTER or RECEIVER trouble
Printer number
VX
Printer Test
TRANSMITTER or RECEIVER test
Printer number
VY
Printer Online
RECEIVER’S printer is now online
Unused
VZ
Printer Offline
RECEIVER’S printer is now offline
Unused
WA
Water Alarm
Water detected at protected premises
Zone or point
WB
Water Bypass
Water detection has been bypassed
Zone or point
WH
Water Alarm Restore Water alarm condition eliminated
Zone or point
WJ
Water Trouble
Restore
Water trouble condition eliminated
Zone or point
WR
Water Restoral
Water alarm/trouble condition has been eliminated
Zone or point
WS
Water Supervisory
Water unsafe water detection system condition
Zone or point
WT
Water Trouble
Water zone disabled by fault
Zone or point
WU
Water Unbypass
Water detection bypass has been removed
Zone or point
XA
Extra Account
Report
CS RECEIVER has received an event from a non-existent account Unused
XE
Extra Point
Panel has sensed an extra point not specified for this site
Point number
XF
Extra RF Point
Panel has sensed an extra RF point not specified for this site
Point number
XH
RF Interference
Restoral
A radio device is no longer detecting RF Interference
Receiver number
XI
Sensor Reset
A user has reset a sensor
Zone or point
XJ
RF Receiver Tamper
Restoral
A Tamper condition at a premises RF Receiver has been restored Receiver number
XL
Low Received Signal
Strength
The RF signal strength of a reported event is below minimum
level
Receiver number
XM
Missing Alarm -
Cross Point
Missing Alarm verified by Cross Point in Alarm (or missing)
Zone or point
XQ
RF Interference
A radio device is detecting RF Interference
Receiver number
XR
Transmitter Battery
Restoral
Low battery has been corrected
Zone or point
XS
RF Receiver Tamper A Tamper condition at a premises receiver is detected
Receiver number
XT
Transmitter Battery
Trouble
Low battery in wireless transmitter
Zone or point
XW
Forced Point
A point was forced out of the system at arm time
Zone or point
XX
Fail to Test
A specific test from a panel was not received
Unused
YA
Bell Fault
A trouble condition has been detected on a Local Bell, Siren, or
Annunciator
Unused
YB
Busy Seconds
Percent of time receiver's line card is on-line
Line card number
YC
Communications Fail RECEIVER and TRANSMITTER
Unused
YD
Receiver Line Card
Trouble
A line card identified by the passed address is in trouble
Line card number
YE
Receiver Line Card
Restored
A line card identified by the passed address is restored
Line card number
YF
Parameter
Checksum Fail
System data corrupted
Unused
YG
Parameter Changed
A TRANSMITTER’S parameters have been changed
Unused
YH
Bell Restored
A trouble condition has been restored on a Local Bell, Siren, or
Annunciator
Unused
YI
Overcurrent Trouble An Expansion Device has detected an overcurrent condition
Unused
YJ
Overcurrent Restore An Expansion Device has restored from an overcurrent condition
Unused
Data Code Short Description
Long Description
Address Field