Operation
Operating Manual PSSu E F 2DOR 8(-T)(-R)
21334-EN-13
| 28
7
Operation
NOTICE
The safety function should be checked after initial commissioning and each
time the plant/machine is changed. The safety functions may only be
checked by qualified personnel.
When the relay outputs are switched on, the mechanical contact on the relay cannot be
tested automatically. Depending on the operational environment, measures to detect the
non-opening of switching elements may be required under some circumstances.
When the product is used in accordance with the European Machinery Directive, a check
must be carried out to ensure that the safety contacts on the relay outputs open correctly.
Start the device again or open the safety contacts (switch off output), so that the internal
diagnostics can check the correct opening of the safety contacts
}
for SIL CL 3/PL e at least 1x per month
}
for SIL CL 2/PL d at least 1x per year
7.1
Messages
A module error is displayed via the "Err" LED (see section entitled "Display elements"). It is
signalled to the head module and then entered in the
}
Error stack, with PSSu in system environment A
}
Diagnostic log, with PSSu in system environment B.
of the head module.
The module can detect the following errors:
Module error
Explanation
Remedy
Start-up error
Error as the PSSu system starts
up
Change faulty module.
Configuration error
Incorrect module type configured. The configured hardware registry
does not match the actual hard-
ware registry.
FS communication error
Error during FS communication
Change faulty module.
Bus termination error
There is no terminating plate or
there is a bad contact with the
module bus.
Install a terminating plate with in-
tegrated end bracket or insert the
base modules together correctly.
Temperature error: too warm (
1
)
Ambient temperature too high:
Error stack entry/diagnostic log
entry
Ensure there is sufficient ventila-
tion in the control cabinet or pre-
vent overload.
Temperature error: too hot (
1
)
Ambient temperature too high:
Reset the module and stop the af-
fected I/O-Groups (SafetyBUS p)
Ensure there is sufficient ventila-
tion in the control cabinet or pre-
vent overload.
Relay control error
Error during cyclical monitoring
test of the relay coils
Change faulty relay module.