Wiring
Operating Manual PSSu E F 2DOR 8(-T)(-R)
21334-EN-13
| 27
6.4
Function test during commissioning
An error must be simulated for each safety-related output during commissioning: The anti-
cipated error reaction must occur when an output has a short circuit to a supply voltage.
INFORMATION
The short circuit test must be performed on the load and not on the output
terminal.