Wiring
Operating Manual PSSu E F 2DOR 8(-T)(-R)
21334-EN-13
| 24
}
On base modules with screw terminals:
– If you use a multi-strand cable to connect the I/Os, it is recommended that you use
ferrules conforming to Parts 1 and 2 of DIN 46228, 0.14 ... 1.5 mm
2
, Form A or C, al-
though this is not essential. To crimp the ferrules you can use crimp pliers (crimp form
A or C) conforming to EN 60947-1, such as the PZ 1.5 or PZ 6.5 from Weidmüller, for
example.
– Maximum torque setting: 0.8 Nm
}
Use copper wiring.
6.2
Terminal configuration
Base module
Terminal configuration
With C-rail
11: Output O0
Relay contact 1
21: Not assigned
12-22: Output O0
Relay contact 2
(12-22 linked within the base
module)
13-23: C-rail supply
(13-23-33-43 linked within
the base module)
14-24: Not assigned
31: Output O1
Relay contact 1
41: Not assigned
32-42: Output O1
Relay contact 2
(32-42 linked within the base
module)
34-44: Not assigned
21
11
22
12
23
13
24
14
41
31
42
32
43
33
44
34