Installation and wiring
Operating Manual PSEN op4B/1 Series
1003356-EN-02
41
Fix the muting sensor with the small plates
to the mounting profile.
[1]
[2]
[1]
[1] Hexagonal screws for attaching the
mounting profile to the safety light grid
[2] Allen screws for attaching the muting
sensor to the mounting profile
6.4
Installation of external muting sensors
When using external muting sensors, position
}
Sensor B1, with transport in one direction
}
Sensors A2 and B1, with transport in two directions
As closely as possible to the safety light grid (see
Distances between muting sensors in the
application example - 4 muting sensors [
36]
).
6.5
Wiring
6.5.1
General guidelines
}
Never place connection cables close to or in contact with cables with the following char-
acteristics (motor supply, inverter or similar).
– High current ratings,
– Strong current fluctuations.
}
Use separate cables to connect the wires to the OSSDs on different safety light grids.
}
Do not connect contacts OSSD1 and OSSD2 in series or in parallel.
}
Connect the N/C contact on the TEST/START button to the supply voltage on the
safety light grid.
}
Connect the N/C contact on the EDM to the supply voltage on the safety light grid.
}
The safety light grid
is already equipped with internal filter capacitors. We would advise
against using additional external components.