PNOZ s8

Operating Manual PNOZ s8
21400-EN-10

16

Mechanical data

750108

751108

Conductor cross section with
spring-loaded terminals: Flexible
with/without crimp connector

0,2 - 2,5 mm², 24 - 12 AWG

Spring-loaded terminals: Terminal
points per connection

2

Stripping length with spring-loaded
terminals

9 mm

Dimensions

Height

98 mm

100 mm

Width

12,5 mm

12,5 mm

Depth

120 mm

120 mm

Weight

105 g

105 g

Where standards are undated, the 2017-01 latest editions shall apply.

Safety characteristic data

NOTICE

You must comply with the safety-related characteristic data in order to
achieve the required safety level for your plant/machine.

Operating
Mode

EN ISO
13849-1:
2015

PL

EN ISO
13849-1:
2015

Category

EN 62061

SIL CL

EN 62061

PFH

D

 [1/h]

IEC 61511

SIL

IEC 61511

PFD

EN ISO
13849-1:
2015

T

M

 [year]

Safety con-
tacts, in-
stantaneous

PL c

Cat. 3

SIL CL 2

2,00E-07

SIL 2

6,35E-03

20

All the units used within a safety function must be considered when calculating the safety
characteristic data.

INFORMATION

A safety function's SIL/PL values are 

not

 identical to the SIL/PL values of

the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.

Summary of Contents for PNOZ s8

Page 1: ...PNOZ s8 Operating Manual 21400 EN 10 Safety relays...

Page 2: ...nta tion will be gratefully received Source code from third party manufacturers or open source software has been used for some components The relevant licence information is available on the Internet...

Page 3: ...ranty and liability 7 Disposal 7 For your safety 7 Unit features 8 Safety features 8 Block diagram terminal configuration 8 Function description 9 Timing diagram 9 Installation 9 Wiring 10 Preparing f...

Page 4: ...Contents Operating Manual PNOZ s8 21400 EN 10 4 Remove plug in terminals 19 Order reference 19 EC declaration of conformity 19...

Page 5: ...y important is identified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measures t...

Page 6: ...the areas described in this manual Use of the product outside the technical details see Technical details 13 NOTICE EMC compliant electrical installation The product is designed for use in an industri...

Page 7: ...e generic and specialist standards applicable to the spe cific application Warranty and liability All claims to warranty and liability will be rendered invalid if The product was used contrary to the...

Page 8: ...ts the following safety requirements The unit monitors its own output contacts The safety function remains effective in the case of a component failure Earth fault in the feedback loop Detected depend...

Page 9: ...terminator is inserted at the side of the unit Connect base unit and PNOZsigma contact expansion module Remove the plug terminator at the side of the base unit and at the contact expander module Conn...

Page 10: ...chnical details 13 Rl km cable resistance km Use copper wire that can withstand 60 75 C Sufficient fuse protection must be provided on all output contacts with capacitive and in ductive loads Ensure t...

Page 11: ...the mechanical contact on the relay cannot be tested automatically Depending on the operational environment measures to detect the non opening of switching elements may be required under some circums...

Page 12: ...indicators FAULT Diagnostics Internal error unit defective Remedy Switch supply voltage off and then on again change unit if neces sary Faults malfunctions Contact malfunctions If the contacts have w...

Page 13: ...750108 751108 Number 1 1 Voltage at Input circuit DC 24 V 24 V Current at Input circuit DC 65 mA 65 mA Max inrush current impulse Current pulse input circuit 0 6 A 0 6 A Pulse duration input circuit...

Page 14: ...h UL Voltage 240 V AC G P 240 V AC G P With current 3 A 3 A Voltage 24 V DC G P 24 V DC G P With current 3 A 3 A Pilot Duty B300 R300 B300 R300 External contact fuse protection safety contacts In acco...

Page 15: ...947 1 EN 60947 1 Overvoltage category III II III II Pollution degree 2 2 Rated insulation voltage 250 V 250 V Rated impulse withstand voltage 4 kV 4 kV Protection type Housing IP40 IP40 Terminals IP20...

Page 16: ...comply with the safety related characteristic data in order to achieve the required safety level for your plant machine Operating Mode EN ISO 13849 1 2015 PL EN ISO 13849 1 2015 Category EN 62061 SIL...

Page 17: ...in the service life table are not accessible the stated PFH value can be used irrespective of the switching frequency and the load as the PFH value already considers the relay s B10d value as well as...

Page 18: ...e category Max rated impulse withstand voltage 3000 m 150 V II 2 5 kV 100 V III 2 5 kV 4000 m 150 V II 2 5 kV 100 V III 2 5 kV 5000 m 100 V II 1 5 kV 24 V III 0 8 kV Reduction of rated insulation volt...

Page 19: ...nection type Order No PNOZ s8 24 VDC Screw terminals 750 108 PNOZ s8 C 24 VDC Spring loaded terminals 751 108 EC declaration of conformity This product these products meet the requirements of the dire...

Page 20: ...yNET p THE SPIRIT OF SAFETY are registered and protected trademarks of Pilz GmbH Co KG in some countries We would point out that product features may vary from the details stated in this document depe...

Reviews: