PNOZ s8
Operating Manual PNOZ s8
21400-EN-10
14
Relay outputs
750108
751108
Utilisation category of safety con-
tacts
AC1 at
240 V
240 V
Min. current
0,02 A
0,02 A
Max. current
3 A
3 A
Max. power
720 VA
720 VA
DC1 at
24 V
24 V
Min. current
0,02 A
0,02 A
Max. current
3 A
3 A
Max. power
72 W
72 W
Utilisation category
In accordance with the standard
EN 60947-5-1
EN 60947-5-1
Utilisation category of safety con-
tacts
AC15 at
230 V
230 V
Max. current
1,5 A
1,5 A
DC13 (6 cycles/min) at
24 V
24 V
Max. current
1,5 A
1,5 A
Utilisation category in accordance
with UL
Voltage
240 V AC G. P.
240 V AC G. P.
With current
3 A
3 A
Voltage
24 V DC G. P.
24 V DC G. P.
With current
3 A
3 A
Pilot Duty
B300, R300
B300, R300
External contact fuse protection,
safety contacts
In accordance with the standard
EN 60947-5-1
EN 60947-5-1
Blow-out fuse, quick
4 A
4 A
Blow-out fuse, slow
2 A
2 A
Blow-out fuse, gG
4 A
4 A
Circuit breaker 24V AC/DC,
characteristic B/C
2 A
2 A
Conventional thermal current
3 A
3 A
Contact material
AgSnO2
AgSnO2
Times
750108
751108
Switch-on delay
With automatic start after power
on typ.
100 ms
100 ms
With automatic start after power
on max.
150 ms
150 ms
Delay-on de-energisation
With E-STOP typ.
30 ms
30 ms
With E-STOP max.
40 ms
40 ms
With power failure typ.
30 ms
30 ms
With power failure max.
40 ms
40 ms