TECHNICAL MANUAL MT103
41
6.2
Tab. 11 PM/819 MONITOR (FIG. 29 and 30)
PROBLEM
POSSIBLE CAUSES
APPARATUS
REMEDY
Guide ring [20] damaged
R14/A Pre-regulator
Replace
Diaphragm [10] ruptured
(fig. 30)
Replace
Obturator [17] damaged
Replace
Obturator [17] stuck in the open position
204/A Pilot (fig. 30)
Control and clean if necessary
Spring [21] yielded
Replace
Pressure
Reinforced gasket [7] damaged
Replace
increase with Q>0
Ice formation between the reinforced gasket
Increase the gas temperature at the
and the plug
regulator inlet
Dirt between the reinforced gasket and the
Clean and check gas filtering
obturator
Regulator (fig. 29)
Obturator blocked
Clean and check movement
Diaphragm fixed incorrectly
Fix
Downstream sensing line dirty
Clean
Occlusion of pressure chamber vent nozzle
Clean
Obturator guide ring [35] damaged
Replace
Feed too low
Replace the spring [12]
Filter cartridge [13] dirty
Replace
Occlusion by frost
Increase temp. at the preregulator inlet
Occlusion by dirty
R14/A Pre-regulator
Check cartridge [13] filtering level
Diaphragm [10] ruptured
(fig. 30)
Replace
Reinforced gasket [9] swollen
Replace
Pilot feed line broken
Repair
Pressure drop
Diaphragm [16] ruptured
204/A Pilot
Replace
Motorisation line to the regulator broken
(fig. 30)
Repair
Obturator blocked
Clean and check movement
Diaphragm [50] ruptured
Replace
Guide ring [36] damaged
Replace
Breakage or leakage from vent nozzle
Regulator (fig. 29)
Repair
calibrated hole screwa
No pressure upstream
Check cleanliness of line filter
acartridges