TECHNICAL MANUAL MT103
40
PROBLEM
POSSIBLE CAUSES
APPARATUS
REMEDY
Reinforced gasket [7] damaged
Replace
Tightness
Obturator guide ring [35] damaged
Regulator (Fig. 26)
Replace
failure Q=0
Ice formation between the seat and the plug
Increase the gas inlet temperature to
the regulator
Diaphragm [20] ruptured
R14/A/FO
Replace
Diaphragm [10] ruptured
Pre-regulator (Fig. 28)
Replace
Occlusion by dirty
Check cartridge [13] filtering level
Reinforced gasket [9] swollen
Replace
Obturator [17] damaged
Replace
Obturator [17] stuck in the open position
204/A/FO Pilot
Control and clean if necessary
Spring [21] yielded
(Fig. 27)
Replace
Pressure
increase with Q>0
Reinforced gasket [7] damaged
Replace
Ice formation between the seat and the plug
Increase the gas inlet tem. to
the regulator
Dirt between the reinforced gasket and the
Clean and check gas filtering
obturador
Regulator
Obturator blocked
(Fig. 26)
Clean and check movement
Diaphragm fixed incorrectly
Fix
Diaphragm ruptured (50)
Replace
Obturator guide ring [35] damaged
Replace
Diaphragm [50] ruptured
Replace
Feed too low
Replace the spring [12]
Filter cartridge [13] dirty
Replace
Occlusion by temperatura
R14/A/FO
Increase inlet temp. to the preregulator
Occlusion by dirty
Pre-regulator
Check cartridge [13] filtering level
Reinforced gasket [9] swollen
(Fig. 28)
Replace
Pilot feed line broken
Repair
Pressure drop
Diaphragm [16] ruptured
204/A/FO Pilot
Replace
Motorisation line to the regulator broken
(Fig. 27)
Repair
Obturator blocked
Clean and check movement
Diaphragm [50] ruptured
Replace
Guide ring [36] damaged
Regulator (Fig. 26)
Replace
No pressure upstream
Check cleanliness of line filter
cartridges
6.1
Tab. 10 REGULATOR (FIG. 26-27 and 28)