6
MT 237 – EN ed.2015 (Rev.A)
2.0
INSTALLATION
2.1
GENERAL
Before installing the valve, it is necessary to make sure that:
it can be inserted in the forecast space and is sufficiently accessible for performing the following maintenance operations (see
overall dimensions in table 2.1);
the inlet and outlet pipings are on the same level and are able to support the valve weight (see weights table 2.2);
the inlet/outlet connections of the piping are parallel;
the inlet/outlet connections of the regulator are clean and the regulator itself has not been subject to any damages during
transport;
the inlet piping has been cleaned in order to remove any residual impurities such as welding scraps, sand, paint residues, water,
etc.
The arrangement normally forecast is the one shown in fig. 2.
Figure 2
Table 2.1: Overall dimensions in mm (fig. 3)
Code
DN
NPS
A
B
C
D
E
N
DILOCK 507
25x25
1”x1”
100
62
182
92
161
Rp 1/4”
DILOCK 512
25x40
1”x1”1/2
110
65
188
92
161
Rp 1/4”
DILOCK 106
32x32
40x40
50x50
1”1/4x1”1/4
1”1/2x1”1/2
2”x2”
152
198
78
162
//
Rp 1/4”
DILOCK 106
65x65
80x80
100x100
2”1/2x2”1/2
3”x3”
4”x4”
354
287
103
245
//
Rp
1/4”
Table 2.2: Weights in KGF
Code
DN
NPS
KGF
DILOCK 507
25x25
1”x1”
2.8
DILOCK 512
25x40
1”x1”1/2
3
DILOCK 106
32x32
40x40
50x50
1”1/4x1”1/4
1”1/2x1”1/2
2”x2”
2
DILOCK 106
65x65
80x80
100x100
2”1/2x2”1/2
3”x3”
4”x4”
8.8