22
VENTILATION INSTALLATION
IMPORTANT
All exhaust systems are required to have make-up air system that replaces 100% of the exhaust air. Windows, doors, or
other openings into the establishment cannot be used for the purposes of providing make-up air. A separate duct
providing air into the building is required.
WARNING
Negative pressure in the room or a faulty exhaust hood installation could damage the electrical components, these type of
damages are not included covered by your warranty.
WARNING
All ventilation connections must in installed to conform to national, provincial or municipal codes in effect. The type of
ventilation hood must be chosen by a professional as this may vary depending on the distance and the routing between
the oven and the ventilator and the number of elbows used.
WARNING
The Picard kettle must be interlocked with a type 2 venting hood, using a pressure or a vacuum switch (refer to the
electrical diagram on page
:
26). A flue riser of 8” in diameter must be attached to the kettle exhaust. The top of the flue
riser must be 2 feet below the hood.
WARNING
Plan ahead a 60’’ (or more) flexible tube for gas inlet (provided by the client) to avoid damages when moving the
equipment.
Summary of Contents for BK-25N
Page 2: ...2...
Page 4: ...4...
Page 6: ...6...
Page 8: ...8...
Page 9: ...9 LABELS YOU WILL FIND ON YOUR OVEN ATTENTION BR LANT C A U T I O N H O T...
Page 10: ...10...
Page 11: ...11...
Page 12: ...12...
Page 14: ...14...
Page 16: ...16 This page has been left blank intentionally...
Page 17: ...17 SECTION INSTALLATION EXTERNAL DIMENSIONS BK 45...
Page 18: ...18 EXTERNAL DIMENSIONS BK 25...
Page 30: ...30 ELECTRIC PLANS...
Page 31: ...31...
Page 34: ...34 A P P E N D I X...