20
MINIMAL REQUIRED DISTANCE BETWEEN THE KETTLE AND FLAMMABLE
MATERIAL
COMBUSTIBLE AND NON-COMBUSTIBLE MATERIAL
Kettle side
2 inch of clearance
Kettle back (from flue riser)
24 inches of clearance
Kettle floor
0 inch of clearance non-combustible materiel only
Between units
4 inches or clearance
GAS CAPACITY AND PRESSURE
MODEL
ORIFICE
GAS TYPE
CAPACITY
BTU
LINE
PRESSURE
MANIFOLD
PRESSURE
BK-25N
#65
Natural
62 000
4"-6"
WATER
COLUMN
LOW – 1.0” W.C.
HI – 3.5” W.C.
BK-25P
Propane
12”-14” WATER
COLUMN
LOW – W.C.
HI – W.C.
BK-45N
#65
Natural
112 000
4"-6"
WATER
COLUMN
LOW – 1.0” W.C.
HI – 3.5” W.C.
BK-45P
Propane
12”-14” WATER
COLUMN
LOW – W.C.
HI – W.C.
ATTENTION!
The temperature high limit alarm must always be adjusted to 800
°
Fahrenheit or 426
°
Celsius.
NOTE
Picard gas units are manufactured to only be used with the type of gas specified on the rating plates.
The installation must conform to local codes, or in the absence of local codes, to the
ANSI Z223.1 / NFPA 54 (National Fuel Gas Code) CAN/CSA-B149.1 (Natural and or propane gas installation code)
WARNING!
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE COULD RESULT IN
PROPERTY DAMAGE, INJURY OR EVEN DEATH.
Summary of Contents for BK-25N
Page 2: ...2...
Page 4: ...4...
Page 6: ...6...
Page 8: ...8...
Page 9: ...9 LABELS YOU WILL FIND ON YOUR OVEN ATTENTION BR LANT C A U T I O N H O T...
Page 10: ...10...
Page 11: ...11...
Page 12: ...12...
Page 14: ...14...
Page 16: ...16 This page has been left blank intentionally...
Page 17: ...17 SECTION INSTALLATION EXTERNAL DIMENSIONS BK 45...
Page 18: ...18 EXTERNAL DIMENSIONS BK 25...
Page 30: ...30 ELECTRIC PLANS...
Page 31: ...31...
Page 34: ...34 A P P E N D I X...