2.3.1.3  Local Occupancy Override

When the override button is pressed, the "person" icon is solid while the output (

OVR1

 and 

OVR2

) shorts. When the button is released, the icon 

blanks. This functionality is seen when a ground has never been applied to the 

EXT OVR 

pin during the current power cycle. Refer to section 

2.3.1.4 Bypass/External "Person" Icon control for the effect of grounding 

EXT OVR

.

2.3.1.4  Bypass/External "Person" Icon Control

The occupancy "person" icon can be used to display bypass status from the Phoenix valve. Configure the valve's DO to output bypass occupancy 
status then wire the DO between the room unit's 

EXT OVR

 and 

GND

 pins.

Once the DO closes (grounds EXT OVR), the "person" icon will become hollow (unoccupied). The icon will remain hollow until either the DO 
closes again or the local occupancy override button is pushed.

Prior to the first closing of the DO (EXT OVR grounded), the unit will behave as described in 

Local Occupancy Override

 above.

2.4  

Optional Technicians Adjustments

This section details optional adjustments a technician can make for:

Changing the humidity output signal

Adjusting humidity output (ie, offset), and

For the PCS300-x-DOS only:

• Adjusting temperature (i.e., offset)
• Changing temperature units, and
• Changing what is shown on its display

2.4.1  Humidity Output Selection

Moving the jumper on connector J4 will change the humidity output from 4 to 20mA, 0 to 5Vdc or 0 to 10Vdc depending on jumper position. 
Figure 7 below shows the jumper in the 4-20mA position.

Figure 6.    

Humidity output jumpers

2.4.2  Humidity Offset Adjustment: PHS300-x and PCS300-x

Potentiometer R34 (Figure 8) can be used to adjust the humidity output by ±5%. A high accuracy humidity reference is recommended. 

Figure 7.    

R34 relative humidity (%RH) adjustment potentiometer

NOTE

Once the 

EXT OVR

 has been grounded, the "person" icon will display continuously (either solid or hollow depending upon the 

current control). The only way to blank the "person" icon from the display (after 

EXT OVR

 has been switched to ground), is to 

cycle power.

Summary of Contents for PCS300-x

Page 1: ...g recommendations It is recommended that the sensor s be kept at room temperature for at least 24 hours before installation to allow any condensation that may have accumulated due to low temperature d...

Page 2: ...wire through the wall and out of the 1 2 hole leaving about six inches free 6 Pull the wire through the hole in the base plate 7 Secure the base to the drywall anchors using the 6 x 1 inch mounting sc...

Page 3: ...s are possible when AC power wiring is present in the same conduit as the signal lines If you are experiencing any of these difficulties please contact your Phoenix Controls Representative Local and n...

Page 4: ...Terminal Applicable to Option Description OVR1 and OVR2 PCS300 x DOS only O Occupancy override status N O contact output 300 mA 24 Vdc SET1 and SET2 PCS300 x DOS only S Temperature setpoint 0 20 K ou...

Page 5: ...300 mA 30 Vdc SET1 and SET2 PCS300 x DOS only S Temperature setpoint 0 20 K output SEN1 and SEN2 PCS300 x and PCS300 x DOS Temperature sensor 10K 2 thermistor output EXT OVR PCS300 x DOS only D Exter...

Page 6: ...default display shows current temperature toggled every 5 seconds with space humidity When the setpoint slider is moved enough to change the setpoint by 0 5 degrees the setpoint will be displayed as...

Page 7: ...to the first closing of the DO EXT OVR grounded the unit will behave as described in Local Occupancy Override above 2 4 Optional Technicians Adjustments This section details optional adjustments a tec...

Page 8: ...isplay toggles through selections 3 Even when the temperature setpoint is not displayed the terminations SET1 and SET2 are active sending a 0 to 20 K signal out PCS300 x DOS Adjustment Parameters Para...

Page 9: ...emperature Determine that the temperature sensor s wires are connected to the correct controller input terminals and are not loose Check the wires at the sensor and controller for proper connections D...

Page 10: ...Format Default Temperature and Humidity toggled every 5 seconds Temp Setpoint only when slider moved Temp Setpoint Slide pot Cool Warm Down Up Configurable at valve UI Absolute 32 122 F 0 50 C Relativ...

Page 11: ...nction entirely on their own and are not a part of another system or piece of equipment For this reason Phoenix Controls products are exempt from the WEEE Directive Nevertheless Phoenix Controls produ...

Page 12: ...anded 4C Round No Signal 22 Belden 8444 Manhattan M13304 1 White 2 Green 3 Black 4 Red Must be stranded 5C Round No Signal 22 Belden 8445 Manhattan M13305 1 White 2 Brown 3 Black 4 Red 5 Green Must be...

Reviews: