PCS300 S

ERIES

 I

NSTALLATION

 G

UIDE

     3 

OF

 12

2.2  

General Wiring Recommendations

2.2.1  Phoenix Controls Wiring Recommendations

Use cables recommended by Phoenix Controls (refer to 

Phoenix Controls Cables on page 12

).

Stranded wire of at least 22 AWG is strongly recommended for all wire connections. Larger gauge wire may be required for long runs. 

Follow good wiring practices:

Do not run the signal cable in the same conduit or wireway as the power cables.

If the signal cable must cross power cables, it is best to do so at a 90-degree angle.

Maintain a consistent color code or polarity all the way through the wiring system.

All wiring must comply with the National Electric Code (NEC) and local codes. 

Do NOT

 run this device's wiring in the same conduit as AC power wiring of NEC class 1, NEC class 2, NEC class 3 or with wiring used to 

supply highly inductive loads such as motors, contactors and relays. 

Tests show that fluctuating and inaccurate signal levels are possible when AC power wiring is present in the same conduit as the signal lines. 
If you are experiencing any of these difficulties, please contact your Phoenix Controls Representative.

Local and national electrical codes take precedence.

Sensor connections:

Remove the front plate from the back plate to facilitate the wiring process. 

Use a small flat screwdriver to tighten the terminal connector screws once the wires have been inserted.

The board connectors accept wires or flat cables ranging from 22 to 14 AWG (0.64-1.63 mm diameter) per pole. However, power cables 
must remain between 18 and 14 AWG (1.02-1.63 mm diameter).

Power connections:

Power type cables (i.e., for power, 2- and 3-wire voltage and current inputs and outputs, as well as triac outputs) should be kept apart from 
other types of wiring to avoid any ambient noise transmission to other wires. 

Do not connect the universal inputs, analog/digital outputs or common terminals to earth or chassis ground (unless stated otherwise).

CAUTION

Turn off power before any kind of servicing.
Please note that there may be multiple power sources.

CAUTION

Phoenix Controls does not recommend wiring the sensor with power applied as accidental arcing may damage the product and 
will void the warranty.

Summary of Contents for PCS300-x

Page 1: ...g recommendations It is recommended that the sensor s be kept at room temperature for at least 24 hours before installation to allow any condensation that may have accumulated due to low temperature d...

Page 2: ...wire through the wall and out of the 1 2 hole leaving about six inches free 6 Pull the wire through the hole in the base plate 7 Secure the base to the drywall anchors using the 6 x 1 inch mounting sc...

Page 3: ...s are possible when AC power wiring is present in the same conduit as the signal lines If you are experiencing any of these difficulties please contact your Phoenix Controls Representative Local and n...

Page 4: ...Terminal Applicable to Option Description OVR1 and OVR2 PCS300 x DOS only O Occupancy override status N O contact output 300 mA 24 Vdc SET1 and SET2 PCS300 x DOS only S Temperature setpoint 0 20 K ou...

Page 5: ...300 mA 30 Vdc SET1 and SET2 PCS300 x DOS only S Temperature setpoint 0 20 K output SEN1 and SEN2 PCS300 x and PCS300 x DOS Temperature sensor 10K 2 thermistor output EXT OVR PCS300 x DOS only D Exter...

Page 6: ...default display shows current temperature toggled every 5 seconds with space humidity When the setpoint slider is moved enough to change the setpoint by 0 5 degrees the setpoint will be displayed as...

Page 7: ...to the first closing of the DO EXT OVR grounded the unit will behave as described in Local Occupancy Override above 2 4 Optional Technicians Adjustments This section details optional adjustments a tec...

Page 8: ...isplay toggles through selections 3 Even when the temperature setpoint is not displayed the terminations SET1 and SET2 are active sending a 0 to 20 K signal out PCS300 x DOS Adjustment Parameters Para...

Page 9: ...emperature Determine that the temperature sensor s wires are connected to the correct controller input terminals and are not loose Check the wires at the sensor and controller for proper connections D...

Page 10: ...Format Default Temperature and Humidity toggled every 5 seconds Temp Setpoint only when slider moved Temp Setpoint Slide pot Cool Warm Down Up Configurable at valve UI Absolute 32 122 F 0 50 C Relativ...

Page 11: ...nction entirely on their own and are not a part of another system or piece of equipment For this reason Phoenix Controls products are exempt from the WEEE Directive Nevertheless Phoenix Controls produ...

Page 12: ...anded 4C Round No Signal 22 Belden 8444 Manhattan M13304 1 White 2 Green 3 Black 4 Red Must be stranded 5C Round No Signal 22 Belden 8445 Manhattan M13305 1 White 2 Brown 3 Black 4 Red 5 Green Must be...

Reviews: