Configuration and startup
3827_en_B
PHOENIX CONTACT
5
Configuration and startup
5.1
Default settings of the wireless module
All RAD-900-… wireless modules have the same configuration by default upon delivery or
by resetting to the default settings at a later stage.
5.1.1
Resetting to the default settings
The device can be reset to the default settings either manually or using the PSI-CONF
software.
Resetting manually
1.
Disconnect the device from the supply voltage.
2.
Hold down the SET button located on the front of the device and switch the supply
voltage on.
3.
Press and hold the SET button until the DAT LED flashes.
Resetting via PSI-CONF software
1.
Select “Wireless, RAD-900-IFS” on the “Device Selection” page.
2.
Select “Local Device”.
3.
Select “Set device to factory default configuration”.
Table 5-1
Default settings of the wireless module
Parameter
Setting
Operating mode
I/O data (wire in/wire out)
Wireless interface
Net ID
127
RF band
1
Encryption
OFF
Network structure
Star
Device type
Slave
Data rate of the wireless interface
125 kbps
Transmission power
1 W (30 dBm)
In order to be able to cover the largest possible distances, the preamplifier has been
activated and transmission power set to 30 dBm by default. When operating the devices
directly next to one another, the receiver might become overloaded. In this case, remove
the antennas, increase the distance between the devices and antennas or reduce
transmission power using the PSI-CONF software (from page 74 onwards).