Addressing I/O extension modules and RAD-900-DAIO6 with Modbus RTU
3827_en_B
PHOENIX CONTACT
9.5.7
RAD-DO8-IFS process data
I/O module
Module type
ID
Number of
registers
Address area
Function
code
RAD-DO8-IFS
11
hex
02
hex
Outputs
40xx0 ... 40xx1
1
1
xx = I/O-MAP address set using the thumbwheel
fc 03.16
02
hex
Short-circuit
detection
30xx0 ... 30xx1
1
fc 04
30xx1
Short-circuit detection at the digital outputs
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Reserved
X
1
1
Bit 1 = 1:
Short circuit detected at one or several outputs 5 ... 8.
X
2
2
Bit 0 = 1:
Short circuit detected at one or several outputs 1 ... 4.
30xx2 ... 30xx9
Reserved
40xx1
Digital outputs DO1 ... DO8
Channel (high byte)
Channel (low byte)
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Reserved
DO
8
DO
7
DO
6
DO
5
DO
4
DO
3
DO
2
DO
2
Terminal point
5.x
5.x
4.x
4.x
3.x
3.x
2.x
2.x
40xx2 ... 40xx9
Reserved